Tjernlund HST_HS115_HSUL-JC, 1C, 2C Canadian Series (Discontinued) 8504017 Rev 1 09/97 User Manual

Page 5

Advertising
background image

INSTALLATION

VENT SYSTEM TERMINATION

Before installing Power Venter determine location of vent system termination.

TOOLS REQUIRED

• Saber Saw or Cement Drill

• Drill

• 1/8” and 1/4” Drill Bits

• Wood or Masonry Chisel

• Blade Screwdriver or 1/4” Nut Driver • Wire Cutter/Stripper

NOTE: Termination of a Side Wall Vent System with a device other than the Tjernlund VH1 Series Vent Hood could affect system

performance and result in a possible safety hazard. Consult Vent Hood instructions for complete installation details.

If possible, locate the Vent Hood on a wall that does not face the direction of prevailing winds. This will diminish the possi-
bility of appliance interruption during periods of extreme winds and prevent oil odors caused by backdrafts.

If possible, locate the Vent Hood no closer than 3 feet from an inside corner of an L-shaped structure.

CODE REQUIREMENTS

• A venting system shall not terminate underneath a veranda, porch, or deck, or above a paved sidewalk or a paved driveway that is

located between two buildings, and that serves both buildings.

• The exit terminals of mechanical draft systems shall not be less than 2.13m (7ft) above grade when located adjacent to a paved

sidewalk or driveway.

• A venting system shall not direct flue gases towards brickwork, siding, or other construction, in such a manner that may cause

damage from heat or condensate from the flue gases.

• A vent system shall not direct flue gases so as to jeopardize people, overheat combustible structures, or enter buildings.

A venting system shall not terminate within 1.8 m (6ft) of the following:
A window, door or mechanical air supply inlet of any building, including soffit openings
• A gas service regulator vent outlet
• A combustion air inlet
• A property line
• A direction facing combustible materials or openings of surrounding buildings

A venting system shall not terminate within 1m (3ft) of the following:
• Above a gas meter/regulator assembly within 1m (3ft) horizontally of the vertical centreline of the regulator
• A oil tank or an oil tankfill inlet
• The inside corner of an L-shaped structure

A venting system shall not terminate within .3m (1ft) of the following:
• Above grade level or any surface that may support snow, ice, or debris

4

For oil installations do not terminate HS-Series Power Venters on vinyl siding because temperatures can easily exceed 66

0

C.

(150

0

F.). The SideShot® is the only Tjernlund Power Venter recommended for termination on vinyl siding when using oil.