MODEL SELECTION TABLE

INSTALLATION RESTRICTIONS

Failure to install, maintain and/or operate the Power Venter in accordance with manufacturer's instructions may result in conditions
which can produce bodily injury and property damage.

The Power Venter must be installed by a qualified installer in accordance with these instructions and all local codes or in their
absence in accordance with the latest edition of The National Fuel Gas Code (NFPA #54), The latest edition of the National Electrical
Code (NFPA#70) and the Occupational Safety and Health Act (OSHA) when applicable. Improper installation can create a hazardous
condition such as an explosion, fire, electrical shock or carbon monoxide poisoning resulting in property damage, personal injury or
death.

Disconnect the power supply when making wiring connections or when working around the fan wheel and motor. Failure to do so can
result in electrical shock, personal injury, death or property damage.

1. The Power Venter may only be installed on Natural Gas or LP Gas appliances.

2. The Power Venter may not be installed on incinerators, incinerating toilets, condensing-type appliances or solid-fuel burning

appliances.

3. The Power Venter shall not be installed on an appliance with an automatic valve having a manual opener unless the manual

opener has been rendered inoperative or the automatic valve has been replaced with a valve not equipped with a manual opener.

4. The Power Venter may only be installed on appliance equipped with a draft hood, draft diverter or barometric draft control.