PRE / POST PURGE AND PROVER STATUS CHECK DIP SWITCH SETTINGS

Remove power to UC1 and heating equipment when installing, servicing or changing dip switch settings. Failure to do so may result in
personal injury and/or equipment damage. LED #5 (RED) should not be on if 115 VAC supply power is removed from the control.

Pre-purge
Used for a Venter with longer vent runs to get draft fully established throughout the vent system prior to burner ignition. Also benefi-
cial for negative pressure prone environments. IMPORTANT: Pre-purge settings must be shorter than flame sensor lockout time
unless wired prior to flame sensor (i.e. aquastat / thermostat).

Post-purge
A Venter post-purge has been factory set at 2 minutes. Confirm that dip switch #5 is in the up or "on" position. A longer post-purge
may be necessary for longer vent runs or high heat retention, refractory lined combustion chambers. A shorter post-purge may be desired
for shorter vent runs or when using the UC1 to control a combustion air In-Forcer.

Pre-Purge

Post-Purge

Prover Status
Check Activated

DIP SWITCH NUMBERING

1

ON

ON

ON

PRE-PURGE SETTINGS

ON

POST-PURGE SETTINGS

ON

P1 & P2 FAN PROVER SAFETY CIRCUIT “OPEN” UPON APPLIANCE CALL

The Prover Status Check is activated from the factory. When activated the UC1 Universal Control
checks across P1 & P2 safety circuit (Venter Fan Prover) to verify that the Fan Prover switch is
“Open” upon a call for heat and not stuck “Closed”. IMPORTANT: This must always be in the
down “Activated” position when side wall venting.

Prover Status
Check Activated

2

3

4

5 6

7 8

9

9

1 2

1 2

1 2

1 2

0 Seconds

15 Seconds

30 Seconds

60 Seconds

PRE-PURGE SETTINGS

4

3

4

8

6

5

7

3

5 6 7 8

3 4 5 6 7 8

3

7

5

4

6

8

4

3

4

8

6

5

7

3

5 6 7 8

3 4 5 6 7 8

4 Minutes

8 Minutes

16 Minutes

1 Minute

0 Seconds

30 Seconds

2 Minutes

P1 & P2 FAN PROVER SAFETY CIRCUIT "OPEN" UPON APPLIANCE CALL