IMPORTANT: The Fan Proving Switch must be mounted so the diaphragm is in a vertical postion.

1. Mount Fan Prover in a vertical position within 4 feet of the Power Venter so 5 foot sensing tube can be trimmed if necessary. Do

not mount the Fan Proving Switch on a heat source that exceeds 140oF. Examples of improper mounting surfaces include vent
pipe, venter, top of heater casing or any place where radiant or convective heat would exceed 140oF.

2. Connect the 1/4” aluminum tubing from the Fan Proving Switch to the Power Venter housing using supplied fittings. The factory

calibrated sensing tube length and compression fittings are critical for proper operation of the Fan Proving Switch. If it is necessary
to alter the sensing tube length, ONLY trim sensing tube portion that is on the exterior of the housing. IMPORTANT: DO NOT trim
the sensing tube portion that will be mounted in the interior of the housing because Fan Prover will not sense the proper pressure.
Sensing tube assembly with factory calibrated length must be used for Fan Prover to work properly!

TYPICAL UC1, FAN PROVER AND VENTER INSTALLATION

WIRING

All wiring from the Power Venter to the appliance must be in compliance with the local codes or in their absence, the National Electric
Code (NFPA #70).

All wiring from the Power Venter to the appliance must be appropriate class 1 wiring as follows: Installed in rigid metal conduit, inter-
mediate metal conduit, rigid non-metallic conduit, electrical metallic tubing, Type MI Cable or be otherwise suitably protected from
physical damage.

SEQUENCE OF OPERATION WITH UC1 UNIVERSAL CONTROL AND 24 VAC OR 115 VAC HEATER CONTROL CIRCUIT:

Control signal from thermostat, aquastat, power burner or gas valve is intercepted and routed to terminal “1” on UC1 terminal strip.
When terminal “1” is energized with either 24 VAC or 115 VAC, the Venter motor is energized. After draft is established, the Fan
Proving Switch closes within 5 to 10 seconds energizing terminal “4”, which completes the circuit allowing burner to fire. NOTE: If a
Venter pre-purge is selected, the burner will not fire until the pre-purge time is finished. The Venter will continue to run after the burn-
er has finished firing for the set post-purge time cycle. The UC1 is set for a 2 minute post-purge time period from the factory. See
“Pre / Post-Purge Settings” on page 5 for details.

The "1" input terminal on the UC1 can accept either a 24 VAC or 115 VAC control signal. IMPORTANT: The RED voltage
jumper must be positioned based on appliance interlock voltage. For most furnace applications it may be easier to interlock with the
24 VAC thermostat circuit. For most boiler applications it may be easiest to interlock with the 115 VAC aquastat or burner motor cir-
cuit. Choose the interlock method that best fits your application. If using the “DRY” contact activation method, use terminals A & B on
UC1 control and position the RED voltage jumper tab in the “DRY” position. See millivolt appliance interlock diagram for further infor-
mation.

The steps listed under each diagram are intended as a supplement to the diagram. Wiring colors or designations may vary by manu-
facturer. If you are unable to wire the UC1 as outlined in these instructions, call Tjernlund’s Customer Service Department toll free at
1-800-255-4208 for assistance.

IMPORTANT: To reset faults, verify fault by checking the LEDs and then remove call for heat.

FAN PROVER

VENTER

UC1

5 FT. LENGTH PROVIDED

UNLESS ADDITIONAL CONDUIT,

(MINIMUM 14 GAGE)

2 FT. MAXIMUM LENGTH UNLESS ADDITIONAL CONDUIT,

J-BOX AND WIRE ARE ADDED (MINIMUM 14 GAGE)

INSTALLER-SUPPLIED

115 VAC CONNECTION

BURNER INTERLOCK

CONNECTION

INSTALLER-SUPPLIED

2 FT. MAXIMUM LENGTH

ALUMINUM SENSING TUBE

SIDE OF SENSING TUBE

DO NOT ALTER THIS

HOUSING WALL

SENSING TUBE

ASSEMBLY

SENSING TUBE

COMPRESSION RING

BRASS ELBOW FITTING

COMPRESSION RING

J-BOX AND WIRE ARE ADDED

IMPORTANT: As viewed from the opposite end of the shaft (rear of motor), the motor should rotate clockwise.

IMPORTANT:
Do not connect 5 foot section
of aluminum tubing directly to
Venter housing. Sensing
tube assembly provided with
factory calibrated length
must be used or Fan Prover
will not work properly.