Troubleshooting guide, Unit does not run/power up, Cellar temperature is to warm – Vintage Cellars Platinum MIni Split Tech Manual User Manual

Page 36: System runs constantly

Advertising
background image

Page 34 | 1-800-343-9463

MPS

033114

TROUBLESHOOTING GUIDE

Unit has ice forming on the Evaporator Unit (Fan Coil Unit)

Possible Cause

Solution

Evaporator filter or coil is dirty.

Remove the filter and wash, then clean the coil with a vacuum.

If coil is very dirty, use a spray bottle with a small amount of

liquid dish washing detergent or coil cleaner. Spray coil, let set

for 5 min, then flush with fresh water.

There is something blocking the supply and or return air

Remove blockage

The evaporator fan is not turning on.

Call a service tech to troubleshoot

The Evaporator Unit (Fan Coil Unit) has not gone through

its anti-frost sequence, yet.

Check for ice in the depth of the coil. Melt with blow drier

until coil is warm to the touch. Soak up water with a towel.

If Evaporator Unit (Fan Coil Unit) continues to ice.

Observe ice formation pattern. If only part way up the coil

face, the system could be low on refrigerant. If all the way

up, the coil may be dirty or airflow is blocked.

Unit does not run/power up

Possible Cause

Solution

Evaporator Unit (Fan Coil Unit) is not plugged in

Make sure the unit is plugged into an outlet

Power switch not on

Turn unit on by pressing the power button on the control

Line voltage is incorrect rating for the system

Check line voltage to make sure there is 110v/120v

Bottle at set point

Lower set point

Thermostat not calling for cooling

Lower set point

Faulty thermostat or wiring

Call Customer Service at 1-800-343-9463

Cellar Temperature is to Warm

Possible Cause

Solution

The temperature or the room condensing unit is

exhausting to has exceeded 110°F

Intake temperature needs to drop below 85°.

The system is undersized for the cellar.

Order correct size system

There is something blocking the supply and/or return air,

on the Evaporator Unit (Fan Coil Unit) or the Condensing

Unit.

Remove air flow obstruction

Evaporator Unit (Fan Coil Unit) is mounted too low in the

cellar

Re-Locate unit so the distance from the ceiling and top of

the unit is no more than 18”

One or more of the fans are not turning on.

Please contact the installing technician to troubleshoot.

Compressor is not turning on.

Please contact the installing technician to troubleshoot.

Compressor keeps cycling on overload

Make sure all fans are working and there are no airflow

obstruction.

Poor seal around door or other areas requiring a seal

(around the unit, wall joints, etc)

Make sure there are no air gaps around the door. If door

seal is damaged, replace it.

Controller set too high

Lower the set point.

Evaporator coil is frosted or iced up

Observe ice formation pattern. If only part way up the

coil face, Evaporator Unit (Fan Coil Unit) could be low on

refrigerant. If so, contact your installing technician to assist

with troubleshooting.

System Runs Constantly

Possible Cause

Solution

Leaky door seal or poorly insulated cellar.

Fix leaky door seal and insulate cellar in accordance with

this manual. (Page 9)

Advertising