Carrier 17EX User Manual

Page 103

Advertising
background image

Table 21 — Marine Waterbox Cover Weights*

HEAT EXCHANGER

SIZE

DESIGN MAXIMUM WATER PRESSURE

COOLER

CONDENSER

psi

kPa

lb

kg

lb

kg

45 - 48

150

1034

2236

1015

1275

579

300

2068

3060

1389

1660

754

55 - 57

150

1034

1643

746

300

2068

2243

1018

*Heat exchangers with marine waterboxes have heavier dry and operating weights than heat exchangers

with nozzle-in-head waterboxes.

Table 22 — NIH Waterbox Cover Weights*

HEAT EXCHANGER

SIZE

PASSES

DESIGN MAXIMUM WATER PRESSURE

COOLER

CONDENSER

psi

kPa

lb

kg

lb

kg

45 - 48

1

150

1034

2997

1361

1735

788

300

2068

4225

1918

2510

1140

2†

150

1034

2984

1355

1885

856

300

2068

4188

1901

2590

1176

3

150

1034

3035

1378

1777

807

300

2068

4244

1927

2539

1153

55 - 57

1

150

1034

2032

923

300

2068

2940

1335

2†

150

1034

2649

1203

300

2068

3640

1653

3

150

1034

300

2068

NIH — Nozzle-in-Head

*The 150 psig (1034 kPa) waterbox cover weights are included in the dry weight shown in Table 15.
†Two different waterbox covers are present on 2-pass chillers. The weight shown in this table represents the

weight of the waterbox cover that contains the nozzles. A blank waterbox cover is also present on 2-pass
units. The weight of the blank waterbox cover is identical to the weight of the same size marine waterbox
cover. Refer to Table 21.

Table 23 — Approximate Refrigerant (HCFC-134a) Charge*

COOLER

SIZE

CONDENSER

SIZE

TOTAL CHILLER

CHARGE

lb

kg

45

45

4100

1860

46
47
55

4320

1960

56
57

46

45

4200

1905

46
47
55

4420

2005

56
57

47

45

4300

1950

46
47
55

4520

2050

56
57

48

45

4580

2077

46
47
55

4800

2177

56
57

*Total chiller refrigerant charge includes the cooler, condenser, and economizer charges.

NOTE: Regulations mandate that chiller shipping charge is limited to 7500 lb (3402 kg).

103