LEGEND

CB

— Circuit Breaker

COMM — Communications
N.O.

— Normally Open

N.C.

— Normally Closed

O.L.

— Overload

PR

— Pilot Relay

RLA

— Rated Load Amps

SMM

— Starter Management Module

TB

— Terminal Block

Starter Vendor Supplied Wiring
Field Wiring
Carrier Factory Wiring

NOTE: Voltage to terminals LL1 and LL2 comes from a control trans-
former in a starter built to Carrier specifications. Do not connect an
outside source of control power to the compressor motor starter (ter-
minals LL1 and LL2). An outside power source will produce danger-
ous voltage at the line side of the starter, because supplying voltage
at the transformer secondary terminals produces input level voltage
at the transformer primary terminals.

Fig. 59 — Elementary Wiring Diagram for Starter Management Module (SMM) and Control Interface Between

Starter and Chiller Power Panel (For Low and Medium Voltage Free-Standing Starters)