INSTALLATION CONSIDERATIONS

Power

This control is powered by 24VAC only. It requires 24VAC (Rh and/or Rc and C

terminals) of the low−voltage transformer to be connected to it for proper

operation. It will not operate without these 2 connections. Rh and Rc are

connected via PCB breakout jumper. See Fig. 1. For applications using two

24VAC transformers, one in the indoor unit and one in the outdoor unit, connect

the common from each to the C terminal. Connect R from the indoor unit to the

Rh terminal. Connect R from the outdoor unit to the Rc terminal. Then, break

jumper on the circuit board. The W and HUM signals are taken from the Rh

power and the G signal is taken from the Rc power. If Thermidistat Control has

been installed in a two−transformer application that is later changed to a

single−transformer installation, installer must install a field supplied jumper

between Rc and Rh. Depending on the installation, up to 14 wires may be

required. Installation as two−piece unit is recommended. Only 2 wires are

required for connection between Display Module and Equipment Control

Module. These two wires (V+ and Vg) do not provide ordinary 24VAC. They

carry a combination of power and communications data that is unique to these

products.