Heat/Cool Setpoints (Desired Temperature)
A minimum difference of 1

_ and maximum of 6_ is enforced between heating

and cooling desired temperatures. This is done by allowing 1 setting to “push”

the other, to maintain this difference. This difference is adjustable via

Configuration Option 11.

Equipment On Indicators

When cooling equipment is on, a COOL ON icon is displayed. While cooling

equipment operation is delayed by the time guard or cycle timer, COOL ON will

flash. The same is true for HEAT ON icon.
During second stage compressor operation a “2” will be displayed with the

HEAT ON or COOL ON icon. This is displayed when the Thermidistat Control

is configured as H2, A2, or h2.
When the W is energized in a heat pump or Hybrid Heat system, the “auxiliary

heat on” icon will be displayed.
Humidify and Dehumidify Indicators
When the Display Module door is closed, the humidify icon will be displayed

when humidification is active and the dehumidify icon will be displayed when

dehumidification is active.
Auto Changeover
When auto changeover mode is selected, a change from heat to cool (or vice

versa) will not occur until an opposite mode demand has existed for 20 minutes.

If setpoint is changed, 20−minute requirement is deleted.
Emergency Heat Mode
When Thermidistat Control is configured as a heat pump and emergency heat is

selected, all Y signals are locked out, and W becomes energized upon a call for

heat.