PNOZ s4

Operating Manual PNOZ s4
21396­EN­13

11

Operation

The unit is ready for operation when the Power LED is permanently lit.

LEDs indicate the status and errors during operation:

LED on

LED flashes

INFORMATION

Status indicators and error indicators may occur independently. In the case
of an error display, the "Fault" LED will light or flash (exception: "Supply
voltage too low"). An LED that is also flashing indicates the potential cause
of the error. An LED that is lit and is static indicates a normal operating
status. Several status indicators and error indicators may occur simultan­
eously.

Status indicators

Power 
Supply voltage is present.

In1 
Input circuit at S12 is closed.

In2 
Input circuit at S22 is closed.

Out
Safety contacts are closed and semiconductor output Y32 carries a high signal.

Reset 
24 V DC is present at S34.

Error indicators

All LEDs off
Diagnostics: Short across contacts/earth fault; unit switched off

}

Remedy: Rectify short across contacts/earth fault, switch off supply voltage
for 1 min.

Fault 
Diagnostics: Plug terminator not connected

}

Remedy: Insert plug terminator, switch supply voltage off and then on
again.