5 test pulse outputs t0, t1, Test pulse outputs t0, t1 – Pilz PNOZ s50 C User Manual
Page 20

Function description
Operating Manual PNOZ s50
1002194EN02
20
Tover
U
B1B2
U
Avg
S35, S36
Y10, Y11
Y20, Y21
01+, 02+
t
t
Y1, Y2
t
Ton
Toff
ton
toff
O4, O5
t
Fig.: Ventilation and application time
Legend:
}
Y10, Y11, Y20, Y21: Safe inputs to switch the outputs O1+/O1, O2+/O2
}
O1+, O2+: Safe outputs, power circuit 1 and 2
}
U
B1B2
: Supply voltage to the power circuits
}
t
on
: Switch on power circuit
}
t
over
: Configured overexcitation time
}
t
off
: Switch off power circuit
}
U
Avg
: Configured reduced voltage (arithmetic mean of the voltage at the outputs once
the overexcitation time has elapsed)
}
Y1, Y2: Feedback loops
}
T
on
: Configured duration of max. ventilation time
}
T
off
: Configured duration of max. application time
}
O4, O5: Failsafe outputs for status of the load, change in state after T
on
and T
off
have
elapsed
4.2.5
Test pulse outputs T0, T1
Feedback loops Y1 and Y2 can be assigned test pulses. The PNOZ s50 has 2 test pulse
outputs, T0 and T1.
INFORMATION
The feedback loop can only use test pulses if mechanical switches are used
to feed back the switch status.