Evaporator Fan Motor Specifications − 48PM16−28 (cont)

UNIT

48PM

DRIVE

ORIENTATION

VOLTAGE

EFFICIENCY %

MAX BHP

MAX AMPS

24

Low

Vertical

208

85.8

4.26

10.6

230

85.8

4.26

9.6

460

85.8

4.26

4.8

575

87.5

5.75

6.0

Mid-Low

Vertical

208

87.5

5.37

15.8

230

87.5

5.75

15.4

460

87.5

5.75

7.7

575

87.5

5.75

6.0

Mid-High

Vertical

208

88.5

7.66

22.0

230

88.5

8.51

22.0

460

88.5

8.63

11.6

575

88.5

8.63

9.4

High

Vertical

208

89.5

9.94

28.0

230

89.5

10.45

28.0

460

89.5

11.19

15.0

575

89.5

11.50

12.0

Low

Horizontal

208

N/A

N/A

N/A

230

N/A

N/A

N/A

460

N/A

N/A

N/A

575

N/A

N/A

N/A

Mid-Low

Horizontal

208

85.8

4.26

10.6

230

85.8

4.26

9.6

460

85.8

4.26

4.8

575

87.5

5.75

6.0

Mid-High

Horizontal

208

87.5

5.37

15.8

230

87.5

5.75

15.4

460

87.5

5.75

7.7

575

87.5

5.75

6.0

High

Horizontal

208

88.5

7.66

22.0

230

88.5

8.51

22.0

460

88.5

8.63

11.6

575

88.5

8.63

9.4

28

Low

Vertical

208

87.5

5.37

15.8

230

87.5

5.75

15.4

460

87.5

5.75

7.7

575

87.5

5.75

6.0

Mid-Low

Vertical

208

87.5

5.37

15.8

230

87.5

5.75

15.4

460

87.5

5.75

7.7

575

87.5

5.75

6.0

Mid-High

Vertical

208

88.5

7.66

22.0

230

88.5

8.51

22.0

460

88.5

8.63

11.6

575

88.5

8.63

9.4

High

Vertical

208

89.5

9.94

28.0

230

89.5

10.45

28.0

460

89.5

11.19

15.0

575

89.5

11.50

12.0

Low

Horizontal

208

87.5

5.37

15.8

230

87.5

5.75

15.4

460

87.5

5.75

7.7

575

87.5

5.75

6.0

Mid-Low

Horizontal

208

87.5

5.37

15.8

230

87.5

5.75

15.4

460

87.5

5.75

7.7

575

87.5

5.75

6.0

Mid-High

Horizontal

208

88.5

7.66

22.0

230

88.5

8.51

22.0

460

88.5

8.63

11.6

575

88.5

8.63

9.4

High

Horizontal

208

89.5

9.94

28.0

230

89.5

10.45

28.0

460

89.5

11.19

15.0

575

89.5

11.50

12.0

NOTES:
1. Extensive motor and electrical testing ensures that the motors can be utilized with confidence up to the maximum applied bhp, watts, and amps. Using the fan
motor up to the maximum ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected.
2. All Indoor-fan motors 5 hp and larger meet the minimum efficiency requirements as established by the Energy Policy Act of 1992 (EPACT) effective October
24, 1997.

48/50PG and PM

Advertising
This manual is related to the following products: