Flow regulation, Flushing, Antifreeze – Carrier AQUAZONE 50PCH User Manual

Page 32: Cooling tower/boiler systems, Warning

Advertising
background image

32

Flow Regulation —

Flow regulation can be accom-

plished by two methods. Most water control valves have a flow

adjustment built into the valve. By measuring the pressure drop

through the unit heat exchanger, the flow rate can be deter-

mined. See Table 26. Adjust the water control valve until the

flow of 1.5 to 2 gpm is achieved. Since the pressure constantly

varies, two pressure gages may be needed in some

applications.

An alternative method is to install a flow control device.

These devices are typically an orifice of plastic material de-

signed to allow a specified flow rate that are mounted on the

outlet of the water control valve. Occasionally these valves

produce a velocity noise that can be reduced by applying some

back pressure. To accomplish this, slightly close the leaving

isolation valve of the well water setup.

Flushing —

Once the piping is complete, units require final

purging and loop charging. A flush cart pump of at least 1.5 hp

is needed to achieve adequate flow velocity in the loop to purge

air and dirt particles from the loop. Flush the loop in both

directions with a high volume of water at a high velocity. Fol-

low the steps below to properly flush the loop:

1. Verify power is off.
2. Fill loop with water from hose through flush cart before

using flush cart pump to ensure an even fill. Do not allow

the water level in the flush cart tank to drop below the

pump inlet line to prevent air from filling the line.

3. Maintain a fluid level in the tank above the return tee to

avoid air entering back into the fluid.

4. Shutting off the return valve that connects into the flush

cart reservoir will allow 50 psig surges to help purge air

pockets. This maintains the pump at 50 psig.

5. To purge, keep the pump at 50 psig until maximum

pumping pressure is reached.

6. Open the return valve to send a pressure surge through

the loop to purge any air pockets in the piping system.

7. A noticeable drop in fluid level will be seen in the flush

cart tank. This is the only indication of air in the loop.

NOTE: If air is purged from the system while using a 10 in.

PVC flush tank, the level drop will only be 1 to 2 in. since

liquids are incompressible. If the level drops more than this,

flushing should continue since air is still being compressed in

the loop. If level is less than 1 to 2 in., reverse the flow.

8. Repeat this procedure until all air is purged.
9. Restore power.

Antifreeze may be added before, during or after the flushing

process. However, depending on when it is added in the

process, it can be wasted. Refer to the Antifreeze section for

more detail.

Loop static pressure will fluctuate with the seasons. Pres-

sures will be higher in the winter months than during the

warmer months. This fluctuation is normal and should be con-

sidered when charging the system initially. Run the unit in

either heating or cooling for several minutes to condition the

loop to a homogenous temperature.

When complete, perform a final flush and pressurize the

loop to a static pressure of 40 to 50 psig for winter months or

15 to 20 psig for summer months.

After pressurization, be sure to remove the plug from the

end of the loop pump motor(s) to allow trapped air to be

discharged and to ensure the motor housing has been flooded.

Be sure the loop flow center provides adequate flow through

the unit by checking pressure drop across the heat exchanger.

Compare the results to the data in Table 26.

Table 26 — Coaxial Water Pressure Drop

Antifreeze —

In areas where entering loop temperatures

drop below 40 F or where piping will be routed through areas

subject to freezing, antifreeze is needed.

Alcohols and glycols are commonly used as antifreeze

agents. Freeze protection should be maintained to 15 F below

the lowest expected entering loop temperature. For example, if

the lowest expected entering loop temperature is 30 F, the

leaving loop temperature would be 22 to 25 F. Therefore, the

freeze protection should be at 15 F (30 F – 15 F = 15 F).

Calculate the total volume of fluid in the piping system. See

Table 27. Use the percentage by volume in Table 28 to

determine the amount of antifreeze to use. Antifreeze concen-

tration should be checked from a well mixed sample using a

hydrometer to measure specific gravity.
FREEZE PROTECTION SELECTION — The 30 F FP1

factory setting (water) should be used to avoid freeze damage

to the unit.

Once antifreeze is selected, the JW3 jumper (FP1) should

be clipped on the control to select the low temperature (anti-

freeze 13 F) set point to avoid nuisance faults.

Cooling Tower/Boiler Systems —

These systems typ-

ically use a common loop temperature maintained at 60 to 90 F.

Carrier recommends using a closed circuit evaporative cooling

tower with a secondary heat exchanger between the tower and

WARNING

To avoid possible injury or death due to electrical shock,

open the power supply disconnect switch and secure it in

an open position before flushing system.

50PC UNIT

SIZE

gpm

L/s

PRESSURE DROP, psi (kPa)

30 F

(-1 C)

50 F

(10 C)

70 F

(21 C))

90 F

(32 C)

006

0.75

0.05

0.5

(3.7)

0.3

(2.3)

0.2

(1.6)

0.2

(1.6)

1.1

0.07

0.8

(5.3)

0.5

(3.5)

0.4

(2.7)

0.3

(2.2)

1.5

0.09

1.3

(8.8)

0.9

(6.1)

0.7

(4.8)

0.6

(4.0)

009

1.1

0.07

1.3

(9.0)

0.6

(4.4)

0.4

(2.8)

0.3

(1.9)

1.8

0.11

2.1 (14.1)

1.4

(9.4)

1.1

(7.4)

0.9

(6.2)

2.3

0.14

3.5 (24.3)

2.6 (17.9)

2.1 (14.7)

1.8 (12.7)

012

1.5

0.09

1.9 (12.8)

1.1

(7.6)

0.8

(5.3)

0.6

(4.1)

2.3

0.15

3.6 (25.0)

2.6 (17.8)

2.1 (14.3)

1.8 (12.1)

3.0

0.19

6.7 (46.1)

5.0 (34.3)

4.1 (28.3)

3.6 (24.5)

015

1.9

0.12

1.0

(6.9)

0.6

(4.4)

0.5

(3.4)

0.4

(2.8)

2.8

0.18

1.8 (12.4)

1.4

(9.3)

1.1

(7.6)

1.0

(6.9)

3.8

0.24

3.3 (22.7)

2.5 (17.5)

2.1 (14.7)

1.9 (13.1)

018

2.3

0.14

2.1 (14.5)

1.4

(9.9)

1.1

(7.6)

0.9

(6.2)

3.4

0.21

3.4 (23.4)

2.6 (17.6)

2.1 (14.7)

1.8 (12.4)

4.5

0.28

5.9 (40.6)

4.6 (31.5)

3.9 (26.9)

3.4 (23.4)

024

3.0

0.19

2.2 (15.2)

1.7 (11.6)

1.4

(9.6)

1.2

(8.3)

4.5

0.28

4.0 (27.6)

3.2 (22.2)

2.8 (19.3)

2.5 (17.2)

6.0

0.38

7.2 (49.6)

5.9 (40.6)

5.2 (35.8)

4.7 (32.4)

030

3.8

0.24

1.3

(9.0)

0.9

(6.1)

0.7

(4.8)

0.6

(4.1)

5.6

0.35

2.3 (15.8)

1.8 (12.5)

1.5 (10.3)

1.4

(9.6)

7.5

0.47

4.2 (28.9)

3.4 (23.2)

2.9 (20.0)

2.6 (17.9)

036

4.5

0.28

1.8 (12.4)

1.4

(9.6)

1.2

(8.3)

1.0

(6.9)

6.8

0.43

3.1 (21.4)

2.4 (16.8)

2.1 (14.7)

1.9 (13.1)

9.0

0.57

5.4 (37.2)

4.4 (30.0)

3.8 (26.2)

3.4 (23.4)

042

5.3

0.33

2.3 (15.8)

1.8 (12.1)

1.5 (10.3)

1.3

(9.0)

7.9

0.50

4.3 (29.6)

3.5 (24.2)

3.1 (26.4)

2.8 (19.3)

10.5

0.66

7.9 (54.4)

6.5 (44.8)

5.7 (39.3)

5.2 (35.8)

048

6.0

0.38

1.8 (12.4)

1.5 (10.1)

1.3

(9.0)

1.2

(8.3)

9.0

0.57

3.4 (23.4)

3.0 (20.4)

2.7 (18.6)

2.6 (17.9)

12.0

0.76

6.2 (42.7)

5.5 (37.9)

5.1 (35.1)

4.8 (35.1)

060

7.5

0.47

3.4 (23.4)

2.8 (19.2)

2.4 (16.5)

2.2 (15.2)

11.3

0.71

6.8 (46.9)

5.9 (40.8)

5.4 (37.2)

5.0 (34.5)

15.0

0.95

12.6 (86.8)

11.1(76.8)

10.3(71.0)

9.6 (66.1)

IMPORTANT: All alcohols should be pre-mixed and

pumped from a reservoir outside of the building or

introduced under water level to prevent fuming.

Advertising