Chapter 4 - Parameter Description [FU1]

42

























[Starting DC Injection Braking Operation]



Note: The DC injection braking parameter does not function

when either FU1-12 or FU1-13 is set to “0”.

Note: FU1-12 [Starting DC Injection Braking Voltage] is also

used as the DC Injection Braking Voltage for the multifunction
input when the multifunction input is set to “DC Braking”.


FU1-20: Maximum Frequency
FU1-21: Base Frequency
FU1-22: Starting Frequency










FU1-20 [Maximum Frequency] is the maximum
output frequency of the inverter. Make sure this
maximum frequency does not exceed the rated
speed of motor.
FU1-21 [Base Frequency] is the frequency where
the inverter outputs its rated voltage. In case of
using a 50Hz motor, set this to 50Hz.
FU1-22 [Starting Frequency] is the frequency
where the inverter starts to output its voltage.












Note: If the command frequency set point is set lower than the

starting frequency, inverter will not output voltage.


FU1-23: Frequency Limit Selection
FU1-24: Low Limit Frequency
FU1-25: High Limit Frequency











Related Functions: FU2-33 [Rated Current of Motor]

FU2-33: The DC current is limited by this parameter.

Output Voltage

Rated

Voltage

Output

Frequency

FU1-22

FU1-21

FU1-20

Output Frequency

Time

FX-CM

ON

Output Voltage

Time

Time

Run Command

FU1-22

FU1-12

t1

t1: FU1-13 [Starting DC Injection
Braking Time]

Output Current

Time