Cleveland Range inverter User Manual
Page 50
 
Chapter 4 - Parameter Description [FU1]
44
FU1-29: Volts/Hz Pattern
 
 
 
 
This is the pattern of voltage/frequency ratio. 
Select the proper V/F pattern according to the 
load. The motor torque is dependent on this V/F 
pattern. 
 
[Linear] pattern is used where constant torque is 
required. This pattern maintains a linear 
volts/frequency ratio from zero to base frequency. 
This pattern is appropriate for constant torque 
applications. 
 
[Square] pattern is used where variable torque is 
required. This pattern maintains squared 
volts/hertz ratio. This pattern is appropriate for 
fans, pumps, etc. 
 
[User V/F] pattern is used for special applications. 
Users can adjust the volts/frequency ratio 
according to the application. This is accomplished 
by setting the voltage and frequency, respectively, 
at four points between starting frequency and 
base frequency. The four points of voltage and 
frequency are set in FU1-30 through FU1-37. 
 
 
 
 
 
 
 
 
 
 
 
[V/F Pattern: ‘Linear’]
 
 
 
 
 
 
 
 
 
 
 
[V/F Pattern: ‘Square’]
 
 
 
 
 
 
 
 
 
 
 
[V/F Pattern: ‘User V/F’]
 
 
FU1-30 ~ FU1-37: User V/F Frequency and Voltage
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Output Voltage
Output 
Frequency
Base Freq.
100%
Output Voltage
Output 
Frequency
Base Freq.
100%
Output Voltage
Output 
Frequency
Base Freq.
100%
FU1-31
FU1-30
FU1-34
FU1-33
FU1-35
FU1-37
FU1-36
FU1-32