Chapter 4 - Parameter Description [FU1]
48
 
 
 
 
FU1-59: Stall Prevention Mode Selection (Bit set) 
FU1-60: Stall Prevention Level 
 
 
 
 
This bit set parameter follows the conventions 
used in I/O-15 and I/O-16 to show the ON (bit set) 
status. 
 
 
 
 
This function is used to prevent the motor from 
stalling by reducing the inverter output frequency 
until the motor current decreases below the stall 
prevention level. This function can be selected for 
each mode of acceleration, steady speed, and 
deceleration via bit combination. 
☞ 
Note: The set value is the percentage of FU2-33 [Rated Motor
Current].
 
FU1-59 [Stall Prevention Mode Selection] 
Setting Range
3
rd
bit 2
nd
bit 1
st
bit
FU1-59 Description
0 0 1 001
Stall Prevention during 
Acceleration 
0 1 0 010
Stall Prevention during Steady 
Speed 
1 0 0 100
Stall Prevention during
Deceleration
When FU1-59 is set to ‘111’, stall prevention works during 
accelerating, steady speed and decelerating. 
 
☞ 
Note: The acceleration and deceleration time may take longer
than the time set in DRV-01, DRV-02 when Stall Prevention is 
selected. 
☞
Note: If stall prevention status persists, inverter may stop
during acceleration.
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
[Stall Prevention during Acceleration]
 
 
 
 
 
 
 
 
 
 
 
 
 
 
[Stall Prevention during Steady Speed]
 
 
 
 
 
 
 
 
 
 
 
[Stall Prevention during Deceleration]
Related Functions: FU2-33 [Rated Motor Current]
Related Functions: FU2-33 [Rated Motor Current]
Output Current
Time
Output Frequency
Time
FU1-60
[Stall level]
FU1-60
[Stall Level]
Output Current
Time
Output Frequency
Time
FU1-60
[Stall Level]
FU1-60
[Stall Level]
Time
DC Link Voltage
Time
Output Frequency
390VDC or
680V DC