3.1.14 Tube Collector Function

If the controller measures an increase of 4 °F compared to
the collector temperature which was last stored, the solar
pump is switched-on for about 30 seconds. After the solar
pump is deactivated the current collector temperature is
stored as new reference value. If the measured temperature
(new reference value) is again exceeded by 4 °F, the solar
pump again switches-on for 30 seconds. If the switch-on
differential is reached during any of these processes the
controller automatically switches over to solar charging.

If the collector temperature drops by 4 °F while the system
fluid is stagnant, the switch-on value for the special tube
collector function will be recalculated.

O TC:
Tube Collector Function
Adjustment range:
OFF / ON

Factory setting: OFF

3.1.13 Recooling Function

This setting is designed to be used in conjunction with the
System Cooling Function, which overrides the maximum
store temperature (S MX) when used. This function will
cool the tank back down to its maximum temperature when
the collector temperature becomes low enough to facilitate
such. This prevents a cumulative overheating condition if the
cooling function needs to be used multiple days in a row.
In order to utilize this function with tube collectors, a heat
rejection loop (heat dump) is necessary.

OREC:
Recooling Option
adjustment range
OFF / ON

Factory setting: OFF

For control and service work the operating mode of the
controller can be manually adjusted by selecting the ad-
justment value HAND, in which the following settings are
available.

3.1.15 Circulator Pump Operating Mode

• HAND

Operating mode
OFF

:

relay off

(flashing) +

AUTO :

relay in automatic operation

ON

:

relay on

(flashing) +

HAND:
Operating Mode
Adjustment range:
OFF/AUTO/ON
Factory setting: AUTO

3.1.16 Language

The menu language can be adjusted in this channel.

dE : German
En : English
• It : Italian
• Fr : French

LANGUAGE
Language Setting
A d j u s t m e n t r a n g e :
d E , E n , I t , F r
Factory setting: En

3.1.17 Units for Temperature Display

The menu units can be adjusted in this channel:

°FAH
°CEL

UNIT:
Temperature Display Units
A d j u s t m e n t r a n g e :
FAH, CEL
Factory setting: FAH