Fig. 11 -- txv sensing bulb location 40ru, Verti cal i nstallati on, Horizontal installatio n – Carrier 40RU User Manual

Page 14

Advertising
background image

14

LEGEND:
TXV – Thermostatic Expansion Valve
NOTE: Component location arrangemetshown for field installation of

sight glasses, solenoid valves, filter driers, and TXV sensing bulbs.
The TXVs and equilizer lines are factory installed.

UPPER

SPLIT

AIRFLOW

LOWER

SPLIT

AIRFLOW

15 DIAMS

MIN

10

DIAMS

8 DIAMS

MIN

TXV

SENSING

BULB

EQUALIZER LINE

SIGHT

GLASS

TXV

SOLENOID

VALVE

FILTER

DRIER

TXV

SENSING

BULB

TXV

8 DIAMS

MIN

15 DIAMS

MIN

10

DIAMS

INDOOR

COIL

EQUALIZER

LINE

Single Circuit Coil Piping Configuration - RU*07, 08

For single compressor condensing units.

Dual Circuit Coil Piping Configuration - RU*12-16

For single compressor condensing units

UPPER

SPLIT

AIRFLOW

15 DIAMS

MIN

10

DIAMS

8 DIAMS

MIN

TXV

SENSING

BULB

EQUALIZER LINE

SIGHT

GLASS

TXV

SOLENOID

VALVE

FILTER

DRIER

C10687

Fig. 9 -- Face--Split Coil Suction and Liquid Line Piping (Typical)

FIRST ON/LAST OFF = B

VERTI CAL I NSTALLATI ON

FIRST ON/LAST OF F = A

HORIZONTAL INSTALLATIO N

C10688

Fig. 10 -- Typical Evaporator Coil Connections (40RU)

LEGEND

TXV — Thermostatic Expansion Valve
NOTE: The 8 o’clock position is shown above.

C10689

Fig. 11 -- TXV Sensing Bulb Location

40RU