CHECK VOLTAGE IMBALANCE

LINE-TO-LINE VOLTS:

AB

V

AC

V

BC

V

(AB + AC + BC)/3 = AVERAGE VOLTAGE =

V

MAXIMUM DEVIATION FROM AVERAGE VOLTAGE =

V

VOLTAGE IMBALANCE = 100 X (MAX DEVIATION)/(AVERAGE VOLTAGE) =

IF OVER 2% VOLTAGE IMBALANCE, DO NOT ATTEMPT TO START SYSTEM!

CALL LOCAL POWER COMPANY FOR ASSISTANCE.

III. START--UP

CHECK INDOOR FAN MOTOR SPEED AND RECORD.

AFTER AT LEAST 10 MINUTES RUNNING TIME, RECORD THE FOLLOWING MEASUREMENTS:

COMP A1

COMP B1

OIL PRESSURE
SUCTION PRESSURE
SUCTION LINE TEMP
DISCHARGE PRESSURE
DISCHARGE LINE TEMP
ENTERING OUTDOOR UNIT AIR TEMP
LEAVING OUTDOOR UNIT AIR TEMP
INDOOR UNIT ENTERING AIR DB TEMP
INDOOR UNIT ENTERING AIR WB TEMP
INDOOR UNIT LEAVING AIR DB TEMP
INDOOR UNIT LEAVING AIR WB TEMP
OUTDOOR UNIT ENTERING WATER TEMP

(40RUS ONLY)
OUTDOOR UNIT LEAVING WATER TEMP

(40RUS ONLY)
INDOOR UNIT ENTERING WATER TEMP

(40RUS ONLY)
INTDOOR UNIT LEAVING WATER TEMP

(40RUS ONLY)

COMPRESSOR AMPS (L1/L2/L3)

____/____/____

____/____/____

CHECK THE COMPRESSOR OIL LEVEL SIGHT GLASSES, ARE THE SIGHT GLASSES SHOWING

OIL LEVEL AT

1

/

8

to

1

/

3

FULL? (Y/N)

NOTES: