Binary coded decimal (bcd) (-b2) -6 – Hardy HI 2151/30WC Single-Scale Controller User Manual

Page 26

Advertising
background image

HI 2151/30WC MANUAL

2-6

•

Response Time

1 millisecond after update

•

Isolation from Main Board

300 VAC or 450 VDC

•

Update

50 milliseconds (20 times/sec.)

•

Voltage Out

•

Range

0 - 5 VDC, 0-10 VDC (or reverse of these)

•

Max Current

5 ma (2 K ohm load @ 10 V)

•

Temp. Stability

10 ppm/C or 4 mV total from 30 to 120 degrees F

•

Current Out

•

Range
0 - 20 mA, 4-20 mA (or reverse of these)

•

Max Voltage
12 V allowing 0 - 600 ohm load at 20 mA

•

Mating Connector
6 pin Phoenix

Binary Coded Decimal
(BCD) (-B2)

•

Resolution

6 digits

•

Data Drive

15 LSTTL loads (6 mA total)

•

Print/Not Print Drive

10 LSTTL loads (4 mA)

•

Transmit Distance

50 feet (15.24 meters)

•

Cable

6" 40 pin right angle to 37 pin Dshell Connector. Use with -B6 and
-B7 Options

Advertising