Chapter 3 - Installation

3-11

J5 Set Point 5

J6 Set Point 6

Pin 1 Lo

Pin 1 Lo

Pin 2 Hi

Pin 2 Hi

J7 Set Point 7

J8 Set Point 8

Pin 1 Lo

Pin 1 Lo

Pin 2 Hi

Pin 2 Hi

•

Use 22 AWG minimum to 12 AWG maximum wire for J3 through
J8.

NOTE:

See Output Option Board Installation for board installation procedures.

CAUTION

THE CONTACTS ON THE SOLID STATE RELAY WILL OPEN IF A POWER
FAILURE OCCURS. A LIT LED INDICATES THAT THE RELAY HAS BEEN
ACTIVATED.

J3 Serial Port Wiring

•

The standard serial port J3 is located on the second board inside the
instrument and is configured either as an RS-232 or RS-422/485
port. (See Section 4.1 for port configuration instructions)

•

The -A model designator in the model number indicates how the
instrument was configured from the factory. (See Table 3-1)

•

Wire size: 22 AWG minimum to 12 AWG maximum

•

For -WS wall mount models, route the wiring to J3 through the
upper left side enclosure access hole when facing the front of the
enclosure.

Remote Functions
Wiring

•

Some functions are level conditions and some are activated by
momentary grounding. Both use the remote functions ground found
on pin 9.

•

Wire Size:

22 AWG Min. to 12 AWG Max. Shielded

-A1

-A2

-A3

J3

RS-232

RS-422

RS-485

Pins

Signal

Signal

Signal

1

Cts

Tx+

Tr+

2

Rts

Tx-

Tr-

3

Rxd

Rx+

N/C

4

Txd

Rx-

N/C

5

Gnd

Gnd

Gnd

TABLE 3-1: FACTORY CONFIGURATION