Initial start-up – AERCO BMK 1.5 LN June 2010 User Manual
Page 37
 
INITIAL START-UP
40. If the oxygen level is not within the specified
range, adjust the level using the ▲ and ▼ 
arrow keys. This will adjust the output 
voltage to the blower motor as indicated on 
the display. Pressing the ▲ arrow key 
increases the oxygen level and pressing the 
▼ arrow key decreases the oxygen level. 
41. Once the oxygen level is within the specified
range at 45%, press the ENTER key to store 
the selected blower output voltage for the 
45% valve position.
42. Press the ▲ arrow key until SET Valve
Position
appears on the C-MORE display.
43. Press the CHANGE key. SET Valve Position
will begin to flash.
44. Press the ▼ arrow key until the SET Valve
Position
reads 30%, then press the ENTER
key.
45. Press the
▼ arrow key until CAL Voltage
30%
is displayed.
46. Press the CHANGE key. CAL Voltage 30%
will begin to flash.
47. The oxygen level at the 30% valve position
should be as shown below. Also, ensure that 
the carbon monoxide (CO) and nitrogen 
oxide (NOx) readings do not exceed the 
values shown.
Combustion Oxygen Level at
30% Valve Position
Oxygen %
± 0.2
Carbon
Monoxide
NOx
7.0 %
<50 ppm
<30 ppm
48. If the oxygen level is not within the specified
range, adjust the level using the ▲ and ▼ 
arrow keys. This will adjust the output 
voltage to the blower motor as indicated on 
the display. Pressing the ▲ arrow key 
increases the oxygen level and pressing the 
▼ arrow key decreases the oxygen level. 
49. Once the oxygen level is within the specified
range at 30%, press the ENTER key to store 
the selected blower output voltage for the 
30% valve position.
50. Press the ▲ arrow key until SET Valve
Position
appears on the C-MORE display.
51. Press the CHANGE key. SET Valve Position
will begin to flash.
52. Press the ▼ arrow key until the SET Valve
Position
reads 16%, then press the ENTER
key.
53. Press the
▼ arrow key until CAL Voltage
16%
is displayed.
54. Press the CHANGE key. CAL Voltage 16%
will begin to flash.
55. The oxygen level at the 16% valve position
should be as shown below. Also, ensure that 
the carbon monoxide (CO) and nitrogen 
oxide (NOx) readings do not exceed the 
values shown.
Combustion Oxygen Level at
16% Valve Position
Oxygen %
± 0.2
Carbon
Monoxide
NOx
8.0 %
<50 ppm
<30 ppm
56. If the oxygen level is not within the specified
range, adjust the level using the ▲ and ▼ 
arrow keys. This will adjust the output 
voltage to the blower motor as indicated on 
the display. Pressing the ▲ arrow key 
increases the oxygen level and pressing the 
▼ arrow key decreases the oxygen level. 
57. Once the oxygen level is within the specified
range at 16%, press the ENTER key to store 
the selected blower output voltage for the 
16% valve position.
58. This completes the natural gas combustion
calibration procedure.
4.4 UNIT REASSEMBLY
Once the combustion calibration adjustments 
are properly set, the unit can be reassembled for 
service operation. 
1. Set the ON/OFF switch in the OFF position.
2. Disconnect AC power from the unit.
3. Shut off the gas supply to the unit.
4. Remove the manometer and barbed fittings
and reinstall the NPT plug using a suitable 
pipe thread compound. 
5. Remove the combustion analyzer probe
from the vent hole. Replace the NPT plug in 
the vent hole using a suitable pipe joint 
compound. 
6. Replace the unit’s side panels and front
door.