Maintenance – AERCO BMK 1.5 LN June 2010 User Manual

Page 53

Advertising
background image

MAINTENANCE

7-3

12

0

IGNITOR-

INJECTOR

GAS

INJECTOR

TUBE

BLOWER

BURNER

PLATE

Figure 7-3

Ignitor-Injector Orientation

8. Reinstall the ignitor-injector in the burner

plate. Torque to 15 ft-lbs. Do not over
tighten.

9. Connect the staged ignition assembly to the

gas injector tube of the ignitor-injector by
securing the compression nut to the elbow
of the staged ignition assembly.

10. Reconnect the ignitor-injector cable.

11. Reinstall the side and top panels on the unit.

7.3 FLAME DETECTOR

The flame detector (part no. 66006) is located
on the burner plate at the top of the unit (see
Figures 7-1 and 7-2). The flame detector may be
hot. Allow the unit to cool sufficiently before
removing the flame detector.

To inspect or replace the flame detector:

1. Set

the ON/OFF switch on the control panel,

to the OFF position. Disconnect AC power
from the unit.

2. Remove the side and top panels from the

unit.

3. Disconnect the flame detector lead wire.

4. Remove the two (2) screws securing the

flame detector to the plate (Figure 7-2 on
previous page). The flame detector is
secured to the burner plate with one (1) #10-
32 screw and one (1) #8-32 screw.

5. Remove the flame detector and gasket from

the burner plate.


6. Thoroughly inspect the flame detector. If

eroded, the detector should be replaced.
Otherwise clean the detector with a fine
emery cloth.

7. Reinstall the flame detector and flame

detector gasket.

8. Reconnect the flame detector lead wire.

9. Reinstall the side and top panels on the unit.

7.4 COMBUSTION CALIBRATION

Combustion settings must be checked at the
intervals shown in Table 7-1 as part of the
maintenance requirements. Refer to Chapter 4
for combustion calibration instructions.

7.5 SAFETY DEVICE TESTING

Systematic and thorough tests of the operating
and safety devices should be performed to
ensure that they are operating as designed.
Certain code requirements, such as ASME
CSD-1, require that these tests be performed on
a scheduled basis. Test schedules must
conform to local jurisdictions. The results of the
tests should be recorded in a log book. See
Chapter 6-Safety Device Testing Procedures.

7.6 BURNER ASSEMBLY INSPECTION

The burner assembly (part no. 24012) is located
at the top of the unit's heat exchanger. The
burner assembly may be hot. Therefore, allow
the unit to cool sufficiently before removing the
burner assembly. It should be noted that the
complete burner assembly also includes the
blower and air/fuel valve assemblies for the unit.

The following parts will be required for
reassembly after burner inspection:

Part No.

Description

81063

Burner Gaskets (Qty=2)

81048

Flame Detector Gasket

81064 Blower

Gasket


To inspect or replace the burner assembly:

1. Set

the

ON/OFF switch on the control panel,

to the OFF position. Disconnect AC power
from the unit and turn off the gas supply.

2. Remove the side and top panels from the

unit.

3. Disconnect the lead wire from the flame

detector installed on the burner plate. See
Figure 7-4.

Advertising