Troubleshooting – AERCO BMK 1.5 LN June 2010 User Manual

Page 61

Advertising
background image

TROUBLESHOOTING

TABLE 8-1. BOILER TROUBLESHOOTING – Continued

FAULT INDICATION

PROBABLE CAUSES

CORRECTIVE ACTION

(continued)

7. Carbon or other debris on Burner.

8. Staged ignition ball valve closed.

9. Staged ignition solenoid valve

doesn’t open.

10. Clogged staged ignition piece.

7. Remove the burner and inspect for any carbon or debris. Clean

and reinstall.

8. Open ball valve downstream of SSOV (see Figure 8-1).

9. When boiler goes to ignition, listen to the solenoid valve for a

clicking sound to ensure it is opening.

10. Remove and inspect staged ignition piece for blockage.

FLAME LOSS

DURING RUN

1. Worn Flame Detector or cracked

ceramic.

2. Defective Regulator.


3. Poor combustion calibration.

4. Debris on burner.

5. Blocked condensate drain.

1. Remove and inspect the Flame Detector for signs of wear or

cracked ceramic. Replace if necessary.

2. Check gas pressure readings using a gauge or manometer into

and out of the Air/Fuel Valve to ensure that the gas pressure
into and out of the valve is correct.

3. Check combustion calibration. Adjust as necessary.

4. Remove the burner and inspect for any carbon or debris. Clean

and reinstall.

5. Remove blockage in condensate drain.

HEAT DEMAND

FAILURE

1. The Heat Demand Relays on the

Ignition/Stepper board failed to
activate when commanded.

2. Relay is activated when not in

Demand

1. Press CLEAR button and restart the unit. If the fault persists,

replace Ignition/Stepper (IGST) Board.

2. Defective relay. Replace IGST Board.

HIGH EXHAUST
TEMPERATURE

1. Defective exhaust sensor.


2. Carboned heat exchanger due to

incorrect combustion calibration

1. Measure the actual exhaust temperature and continuity of the

exhaust sensor. If the exhaust temperature is less than 475

o

F

and the exhaust sensor shows continuity replace the sensor.

2. If exhaust temperature is greater than 500

o

F, check

combustion calibration. Calibrate or repair as necessary.

8-5

Advertising