Control panel operating procedures – AERCO BMK 1.5 LN May 2009 User Manual
Page 27
CONTROL PANEL OPERATING PROCEDURES
Table 3-4. Configuration Menu - Continued
Available Choices or Limits
Menu Item Display
Minimum
Maximum
Default
Failsafe Mode
Shutdown or Constant Setpt
Shutdown
*mA Output 
(See CAUTION) 
Setpoint, Outlet Temp,
Fire Rate Out, Off
*Fire Rate
Out
Low Fire Timer
2 sec.
120 sec.
2 sec.
Setpt Limiting
Enabled or Disabled
Disabled
Setpt Limit Band
0°F
10°F
5°F
*CAUTION
: DO NOT CHANGE mA Output Menu Item from its Default setting.
3.7 TUNING MENU
The Tuning Menu items in Table 3-5 are Factory set for each individual unit. Do not change these menu 
entries unless specifically requested to do so by Factory-Trained personnel. 
Table 3-5. Tuning Menu
Available Choices or Limits
Menu Item Display
Minimum
Maximum
Default
Prop Band
1°F
120°F
70°F
Integral Gain
0.00
2.00
1.00
Derivative Time
0.0 min
2.00 min
0.00 min
Reset Defaults?
Yes
No
Are You Sure?
No
3.8 START SEQUENCE
When the Control Box ON/OFF switch is set to 
the ON position, it checks all pre-purge safety 
switches to ensure they are closed. These 
switches include: 
• Safety Shut-Off Valve Proof of Closure
(POC) switch
• Low Water Level switch 
• High 
Water
Temperature
switch
• High Gas Pressure switch 
• Low Gas Pressure switch 
• Blower Proof switch 
If all of the above switches are closed, the 
READY
light above the ON/OFF switch will light
and the unit will be in the Standby mode.
When there is a demand for heat, the following 
events will occur: 
NOTE
If any of the Pre-Purge safety device 
switches are open, the appropriate fault 
message will be displayed. Also, the 
appropriate fault messages will be displayed 
throughout the start sequence, if the 
required conditions are not observed. 
 
1. The
DEMAND
LED status indicator will light.
2. The unit checks to ensure that the Proof of
Closure (POC) switch in the downstream 
Safety Shut-Off Valve (SSOV) is closed. 
See Figure 3-3 for SSOV locations. 
 
 
3-7