Chapter 5 - mode of operation, Mode of operation, Chapter 5 mode of operation – AERCO BMK 1.5 LN May 2009 User Manual

Page 37

Advertising
background image

MODE OF OPERATION

5-1

CHAPTER 5 MODE OF OPERATION

5.1 INTRODUCTION

The Benchmark 1.5 Boiler is capable of being
operated in any one of six different modes. The
following paragraphs in this Chapter provide
descriptions of each of these operating modes.
Each Benchmark 1.5 Boiler is shipped from the
factory tested and configured for the ordered
mode of operation. All temperature related
parameters are at their factory default values
which work well in most applications. However, it
may be necessary to change certain parameters
to customize the unit to the system environment.
A complete listing and descriptions of the
temperature related parameters are included in
Appendix A. Factory defaults are listed in
Appendix E. After reading this chapter,
parameters can be customized to suit the needs
of the specific application.

5.2 INDOOR/OUTDOOR RESET MODE

This mode of operation is based on outside air
temperatures. As the outside air temperature
decreases, the supply header temperature will
increase and vice versa. For this mode, it is
necessary to install an outside air sensor as well
as select a building reference temperature and a
reset ratio.

5.2.1 Reset Ratio

Reset ratio is an adjustable number from 0.1 to
9.9. Once adjusted, the supply header
temperature will increase by that number for
each degree that the outside air temperature
decreases. For instance, if a reset ratio of 1.6 is
used, for each degree that outside air
temperature decreases the supply header
temperature will increase by 1.6 degrees.

5.2.2 Building Reference Temperature

This is a temperature from 40°F to 230°F. Once
selected, it is the temperature that the system
references to begin increasing its temperature.
For instance, if a reset ratio of 1.6 is used, and
we select a building reference temperature of
70°F, then at an outside temperature of 69°F,
the supply header temperature will increase by
1.6° to 71.6°F.

5.2.3 Outdoor Air Temperature Sensor
Installation

The outdoor air temperature sensor must be
mounted on the North side of the building in an
area where the average outside air temperature
is expected. The sensor must be shielded from
the sun's direct rays, as well as direct
impingement by the elements. If a cover or
shield is used, it must allow free air circulation.
The sensor may be mounted up to two hundred
feet from the unit. Sensor connections are
made at the Input/Output (I/O) Box on the front
of the Benchmark 1.5 Boiler. Connections are
made at the terminals labeled OUTDOOR
SENSOR IN and SENSOR COMMON inside the
I/O Box. Use shielded 18 to 22 AWG wire for
connections. A wiring diagram is provided on
the cover of the I/O Box. Refer to Chapter 2,
paragraph 2.9.1 for additional wiring information.

5.2.4 Indoor/ Outdoor Startup

Startup in the Indoor/Outdoor Reset Mode is
accomplished as follows:

1. Refer to the Indoor/Outdoor reset ratio

charts in Appendix D.

2. Choose the chart corresponding to the

desired Building Reference Temperature.

3. Go down the left column of the chart to the

coldest design outdoor air temperature
expected in your area.

NOTE

A design engineer typically provides
design outdoor air temperature and
supply

header

temperature data

4. Once the design outdoor air temperature is

chosen, go across the chart to the desired
supply header temperature for the design
temperature chosen in step 3.

5. Next, go up that column to the Reset Ratio

row to find the corresponding reset ratio.

6. Access the Configuration Menu and scroll

through it until the display shows Bldg Ref
Temp
. (Building Reference Temperature).

Advertising