CONTROL PANEL OPERATING PROCEDURES

Table 3-6.

Relationship Between Air/Fuel Valve Position and Energy Input For Unit Running On Natural Gas

Fire Rate,

Air/Fuel Valve

Position

(% Open)

Energy Input

(BTU/Hr)

Boiler Energy Input
(% of Full Capacity)

0% 0

0

10% 0

0

16 %

(Stop Level)

75,000 5.0%

20% 157,000 10%
30% 310,000 21%
40% 534,000 36%
50% 783,000 52%
60% 970,000 65%
70% 1,140,000 76%
80% 1,240,000 83%
90% 1,370,000 91%

100% 1,500,000 100%