INITIAL START-UP

4-5

27.

Press the ▲ arrow key until SET Valve
Position
appears on the C-MORE display.

28. Press the CHANGE key. SET Valve Position

will begin to flash.

29. Press the

▼ arrow key until the SET Valve

Position reads 65% and press the ENTER
key.

30. Press the

down ▼ arrow key until CAL

Voltage 65% is displayed.

31. Press the CHANGE key. CAL Voltage 65%

will begin to flash.

32. The oxygen level at the 65% valve position

should be as shown below. Also, ensure that
the carbon monoxide (CO) and nitrogen
oxide (NOx) readings do not exceed the
values shown.

Combustion Oxygen Level at

65% Valve Position

Oxygen %

± 0.2

Carbon

Monoxide

NOx

6.3 %

<50 ppm

<30 ppm

33. If the oxygen level is not within the specified

range, adjust the level using the ▲ and ▼
arrow keys. This will adjust the output
voltage to the blower motor as indicated on

the display. Pressing the ▲ arrow key
increases the oxygen level and pressing the

▼ arrow key decreases the oxygen level.

34. Once the oxygen level is within the specified

range at 65%, press the ENTER key to store
the selected blower output voltage for the
65% valve position.

35.

Press the ▲ arrow key until SET Valve
Position
appears on the C-MORE display.

36. Press the CHANGE key. SET Valve Position

will begin to flash.

37. Press the

▼ arrow key until the SET Valve

Position reads 45%, then press the ENTER
key.

38. Press the

▼ arrow key until CAL Voltage

45% is displayed.

39. Press the CHANGE key. CAL Voltage 45%

will begin to flash.

40. The oxygen level at the 45% valve position

should be as shown. Also, ensure that the
carbon monoxide (CO) and nitrogen oxide
(NOx) readings do not exceed the values
shown.

Combustion Oxygen Level at

45% Valve Position

Oxygen %

± 0.2

Carbon

Monoxide

NOx

6.5 %

<50 ppm

<30 ppm

41. If the oxygen level is not within the specified

range, adjust the level using the ▲ and ▼
arrow keys. This will adjust the output
voltage to the blower motor as indicated on

the display. Pressing the ▲ arrow key
increases the oxygen level and pressing the

▼ arrow key decreases the oxygen level.

42. Once the oxygen level is within the specified

range at 45%, press the ENTER key to store
the selected blower output voltage for the
45% valve position.

43.

Press the ▲ arrow key until SET Valve
Position
appears on the C-MORE display.

44. Press the CHANGE key. SET Valve Position

will begin to flash.

45. Press the

▼ arrow key until the SET Valve

Position reads 30%, then press the ENTER
key.

46. Press the

▼ arrow key until CAL Voltage

30% is displayed.

47. Press the CHANGE key. CAL Voltage 30%

will begin to flash.

48. The oxygen level at the 30% valve position

should be as shown below. Also, ensure that
the carbon monoxide (CO) and nitrogen
oxide (NOx) readings do not exceed the
values shown.

Combustion Oxygen Level at

30% Valve Position

Oxygen %

± 0.2

Carbon

Monoxide

NOx

6.5 %

<50 ppm

<30 ppm

49. If the oxygen level is not within the specified

range, adjust the level using the ▲ and ▼
arrow keys. This will adjust the output
voltage to the blower motor as indicated on

the display. Pressing the ▲ arrow key
increases the oxygen level and pressing the

▼ arrow key decreases the oxygen level.

50. Once the oxygen level is within the specified

range at 30%, press the ENTER key to store
the selected blower output voltage for the
30% valve position.