1 digital alarm switch checks and adjustments, Initial start-up – AERCO BMK 3.0 LN Dual Fuel July 2011 User Manual

Page 42

Advertising
background image

INITIAL START-UP

4-10

Figure 4-7

Over Temperature Limit Switch

Locations

4.6.1 Digital Alarm Switch Checks and
Adjustments

The digital alarm switch settings can be checked
or adjusted using the controls and display on the
front panel of the switch illustrated and
described in Figure 4-8 and Table 4-2

F

Alarm

RST

SET

Limit Control

Figure 4-8

Digital Alarm Switch Front Panel

Table 4-2:

Digital Alarm Switch Controls and Display

CONTROL

or

Display

MEANING

FUNCTION

LED

Display

TEMP

status

Displays current
water
temperature or
setpoint.

RST

RESET

Button

Resets the unit
after an alarm
condition.

UP Button

Increases the
displayed
temperature.

DOWN

Button

Decreases the
displayed
temperature.

SET

SET Button

Used to access
and store
parameters in
the unit.

Perform the following steps to check or adjust
the digital alarm switch settings:

1. Set the ON/OFF to the ON position.

2. Press the SET button on the Digital Alarm

Switch. SP will appear in the display.

3. Press the SET button again. The current

over-temperature limit value stored in
memory will be displayed. (default = 210°F).

4. If the display does not show the required

over-

temperature alarm setting, press the ▲

or ▼ arrow button to change the display to
the desired temperature setting.

5. Once the desired over-temperature alarm

setting (210ºF) is displayed, press the SET
button to store the setting in memory.

6. To calibrate the offset (P1), press and hold

the SET button for 8 seconds on the Digital
Alarm Switch. Access code value 0 should
appear in the display. The switch comes
from the factory with the code set at 0.

RESET BUTTON FOR

MANUAL RESET

TEMPERATURE

LIMIT SWITCH

ADJUSTABLE

TEMPERATURE

LIMIT SWITCH

DIGITAL OVER-

TEMPERATURE

ALARM SWITCH

FUEL

SELECTOR

SWITCH

Advertising