APPENDIX D

D-4

Table D-7. Header Temperature for a Building Reference Temperature of 90F

RESET RATIO

Air

Temp

0.6

0.8

1.0

1.2

1.4

1.6

1.8

2.0

2.2

2.4

90F

90

90

90

90

90

90

90

90

90

90

85F

93

94

95

96

97

98

99

100

101

102

80F

96

98

100

102

104

106

108

110

112

114

75F

99

102

105

108

111

114

117

120

123

126

70F

102

106

110

114

118

122

126

130

134

138

65F

105

110

115

120

125

130

135

140

145

150

60F

108

114

120

126

132

138

144

150

156

162

55F

111

118

125

132

139

146

153

160

167

174

50F

114

122

130

138

146

154

162

170

178

186

45F

117

126

135

144

153

162

171

180

189

198

40F

120

130

140

150

160

170

180

190

200

210

35F

123

134

145

156

167

178

189

200

30F

126

138

150

162

174

186

198

210

25F

129

142

155

168

181

194

207

20F

132

146

160

174

188

202

216

15F

135

150

165

180

195

210

10F

138

154

170

186

202

218

5F

141

158

175

192

209

0F

144

162

180

198

216