CONTROL PANEL OPERATING PROCEDURES

3-6

Table 3-4. Configuration Menu

Available Choices or Limits

Menu Item Display

Minimum

Maximum

Default

Internal Setpt

Lo Temp Limit

Hi Temp Limit

130°F

Unit Type

Boiler

Water Heater

Boiler

Unit Size

0.5 MBTU
1.0 MBTU
1.5 MBTU
2.0 MBTU
2.5 MBTU
3.0 MBTU

1.0 MBTU

Boiler Mode

Constant Setpoint

Remote Setpoint

Direct Drive

Combination

Outdoor Reset

Constant
Setpoint

Remote Signal
(If Mode = Remote
Setpoint, Direct Drive
or Combination)

4 – 20 mA/1 – 5V

0 -20 mA/0 – 5V

PWM Input (BMS)

Network

4 – 20 mA,
1-5V

Bldg Ref Temp
(If Boiler Mode =
Outdoor Reset)

40°F

240°F

70°F

Reset Ratio
(If Boiler Mode =
Outdoor Reset)

0.1

9.9

1.2

Outdoor Sensor

Enabled or Disabled

Disabled

System Start Tmp
(If Outdoor Sensor =
Enabled)

30°F

100°F

60°F

Setpt Lo Limit

40°F

Setpt Hi Limit

60°F

Setpt Hi Limit

Setpt Lo Limit

240°F

200°F

Temp Hi Limit

40°F

240°F

215°F

Max Fire Rate

40%

100%

100%

Pump Delay Timer

0 min

30 min

0 min

Aux Start On Dly

0 sec

120 sec

0 sec

Failsafe Mode

Shutdown or Constant Setpt

Shutdown

mA Output

Setpoint, Outlet Temp,

Fire Rate Out, Off

Off

Lo Fire Timer

2 sec

120 sec

2 sec

Setpt Limiting

Enabled or Disabled

Disabled

Setpt Limit Band

0°F

10°F

5°F