INITIAL START-UP

4-4

12. If the measured oxygen level is within the

range in Table 1, no adjustment is
necessary. Proceed to step 17.

13. If the measured oxygen level is below the

range in Table 1, rotate the differential
regulator adjustment tool counterclockwise
1/4 to 1/2 revolution to decrease gas flow.

14. Wait for the combustion analyzer to settle,

then compare the new oxygen reading to
Table 1. Repeat adjustment until oxygen is
within the specified range.

15. If the measured oxygen level is above the

oxygen range in Table 1, rotate the
differential regulator adjustment tool clock-
wise 1/4 to 1/2 revolution to increase gas
flow.

16. Wait for the analyzer reading to settle, then

compare the new reading to Table 1. Repeat
adjustment until oxygen is within the
specified range.

NOTE:

Adjust only the differential regulator at 30%
control signal; do not adjust the air shutter.

17. Once the oxygen level is within the specified

range at 30%, change the firing rate to 16%.


18. Oxygen levels at the 16% firing rate should

be as shown in Table 2. No adjustment
should be necessary. Contact the Factory if
the oxygen or carbon monoxide levels are
not within the specified range.


Table 2

Combustion Oxygen Levels for a 16%

Firing Rate

Inlet Air

Temp

Oxygen

(+0.2/-1.0)

Carbon

Monoxide

-20°F

<12 %

<50 ppm

0°F

<12 %

<50 ppm

10°F

<12 %

<50 ppm

30°F

<12 %

<50 ppm

50°F

<11 %

<50 ppm

60°F

<11 %

<50 ppm

70°F

<11 %

<50 ppm

80°F

<11 %

<50 ppm

90°F

<10 %

<50 ppm

100°F

<10 %

<50 ppm

19. Change the firing rate to 100%. After the

combustion analyzer has settled, compare
the measured oxygen level with the levels in
Table 3.


20. If the measured oxygen reading is below the

oxygen range in Table 3, loosen the two
bolts that secure the inlet air shutter to the
unit using a 7/16” wrench (see Fig. 4.4).
Open the shutter 1/4” to 1/2” to increase the
oxygen level, then tighten the nuts.


21. Wait for the analyzer to settle then compare

the new oxygen reading to Table 3. Repeat
the inlet air shutter adjustment until the
oxygen is within the specified range. Firmly
tighten the inlet air shutter locking nuts when
finished.

Table 3

Combustion Oxygen Levels for a 100%

Firing Rate

Inlet Air

Temp

Oxygen

(+0.2/-1.0)

Carbon

Monoxide

-20°F

6.5 %

<150 ppm

0°F

6.3 %

<150 ppm

10°F

6.2 %

<150 ppm

30°F

5.8 %

<150 ppm

50°F

5.4 %

<150 ppm

60°F

5.2 %

<150 ppm

70°F

5.0 %

<150 ppm

80°F

4.8 %

<150 ppm

90°F

4.6 %

<150 ppm

100°F

4.4 %

<150 ppm

REMINDER:

At 30% firing rate, adjust only the differential
pressure regulator. At 100% firing rate, adjust
only the inlet air shutter.

BLOWER
OUTLET

BLOWER
INLET

SCREEN

SHUTTER

SHUTTER
LOCKING NUTS

Figure 4.4

Air Shutter Locking Nut Location