Appendix a – AERCO KC1000 Boiler equipped with C-More 2002 User Manual

Page 83

Advertising
background image

APPENDIX A

A-3


BOILER MENU ITEM DESCRIPTIONS - Continued

MENU LEVEL & OPTION

DESCRIPTION

Reset Ratio

Permits setting of Reset Ratio when operating boiler
in the Outdoor Reset Mode. Reset Ratio is
adjustable from 0.1 to 9.9. Default is 1.2.

Outdoor Sensor

Allows outdoor sensor function to be enabled or
disabled. Default is Disabled.

System Start Tmp

If outdoor sensor is enabled in the Configuration
Menu, this menu item allows the system start
temperature to be set from 30°F to 100°F. Default
is 60°F.

Setpoint Lo Limit

Used to set the minimum allowable setpoint (40°F to
Setpoint Hi Limit). Default is 60°F

Setpoint Hi Limit

Used to set the maximum allowable setpoint
(Setpoint Lo Limit to 240°F). Default is 200°F.

Temp Hi Limit

Used to set the maximum allowable outlet
temperature (40°F to 240°F). Any temperature
above this setting will turn off the unit. The
temperature must then drop 5°F below this setting
to allow the unit to run. Default Temp Hi Limit is
215°F.

Max Fire Rate

Sets the maximum allowable fire rate for the unit
(40% to 100%). Default is 100%.

Pump Delay Timer

Specifies the amount of time (0 to 30 min.) to keep
the pump running after the unit turns off. Default is
zero.

Aux Start On Dly

Specifies the amount of time to wait (0 to 120 sec.)
between activating the Aux Relay (due to a
demand) and checking the pre-purge string to start
the boiler. Default is 0 sec.

Failsafe Mode

Allows the Failsafe mode to be set to either
Constant Setpoint or Shutdown. Default is
Shutdown.

mA Output

Can be set to allow this output to monitor Setpoint,
Outlet Temperature, Fire Rate Out or be set to OFF.
Default is OFF.

Lo Fire Timer

Specifies how long (2 to 120 sec.) to remain in the
low fire position after ignition, before going to the
desired output. Default is 2 sec.