Air shutter locking nut location, Initial start-up – AERCO KC1000 Boiler equipped with C-More 2002 User Manual

Page 50

Advertising
background image

INITIAL START-UP

4-4

NOTE:

Adjust only the differential regulator at 30%
control signal; do not adjust the air shutter.

19. When the oxygen level is within the specified

range at 30%, change the firing rate to 13%.


20. The oxygen levels at the 13% firing rate

should be as shown in Table 2. No
adjustment should be necessary. Contact
the factory if the oxygen or carbon monoxide
levels are not within the specified range.

Table 2

Combustion Oxygen Levels for Both a

13% (Natural Gas) and 16% (Propane)

Firing Rate

Inlet Air

Temp

Oxygen

(+0.2/-1.0)

Carbon

Monoxide

-20°F

<12 %

<50 ppm

0°F

<12 %

<50 ppm

10°F

<12 %

<50 ppm

30°F

<12 %

<50 ppm

50°F

<11 %

<50 ppm

60°F

<11 %

<50 ppm

70°F

<11 %

<50 ppm

80°F

<11 %

<50 ppm

90°F

<10 %

<50 ppm

100°F

<10 %

<50 ppm


21. Change the firing rate to 100%. After the

combustion analyzer has settled, compare
the measured oxygen level with the levels in
Table 3.

Table 3

Combustion Oxygen Levels for a 100%

Firing Rate

Inlet Air

Temp

Oxygen

(+0.2/-1.0)

Carbon

Monoxide

-20°F

6.5 %

<150 ppm

0°F

6.3 %

<150 ppm

10°F

6.2 %

<150 ppm

30°F

5.8 %

<150 ppm

50°F

5.4 %

<150 ppm

60°F

5.2 %

<150 ppm

70°F

5.0 %

<150 ppm

80°F

4.8 %

<150 ppm

90°F

4.6 %

<150 ppm

100°F

4.4 %

<150 ppm

22. If the measured oxygen reading is below the

oxygen range in Table 3, loosen the two
bolts that secure the inlet air shutter to the
unit using a 7/16” wrench (see Fig. 4.4).
Open the shutter 1/4” to 1/2” to increase the
oxygen level, then tighten the nuts.

23. Wait for the analyzer to settle then compare

the new oxygen reading to Table 3. Repeat
the inlet air shutter adjustment until the
oxygen is within the specified range. Firmly
tighten the inlet air shutter locking nuts when
finished.


24. If the measured oxygen reading is above the

oxygen range in Table 3, loosen the two
7/16" locking nuts securing the inlet air
shutter.

REMINDER:

At 30% firing rate, adjust only the differential
pressure regulator. At 100% firing rate, adjust
only the inlet air shutter.

BLOWER
OUTLET

BLOWER
INLET

SCREEN

SHUTTER

SHUTTER
LOCKING
NUTS

Figure 4.4

Air Shutter Locking Nut Location


25. Close the air shutter 1/4” to 1/2” to decrease

the oxygen level and tighten the two nuts.


26. Allow the analyzer to settle then compare the

new oxygen reading to Table 3.


27. Repeat the adjustment until the oxygen is

within the specified range. Firmly tighten the
inlet air shutter locking nuts when finished.