10 fault relay, Figure 2.11 i/o box wiring, Installation – AERCO KC1000 Heater Mar 2011 User Manual

Page 16: 1 remote interlock in, 2 delayed interlock, 11 auxiliary relay contacts

Advertising
background image

INSTALLATION

2-8

2.6.9.1 REMOTE INTERLOCK IN

The remote interlock circuit is provided to

remotely start (enable) and stop (disable) the

unit if desired. The circuit is labeled REMOTE

INTL’K IN and is located inside the I/O Box on

the left side of the unit. The circuit is 24 VAC

and comes factory pre-wired closed (jumped).

2.6.9.2 DELAYED INTERLOCK

The delayed interlock is typically used in

conjunction with the auxiliary relay described in

paragraph 2.6.11. This interlock circuit is located

in the purge section of the start string. It can be

connected to the proving device (end switch,

flow switch etc.) of an auxiliary piece of equip-

ment started by the unit’s auxiliary relay. The

delayed interlock must be closed for the heater

to fire. If the delayed interlock is connected to a

proving device that requires time to close

(make), a time delay (Aux Start On Dly) that

holds the start sequence of the unit long enough

for a proving switch to make (close) can be

programmed.

Should the proving switch not prove within the

programmed time frame, the unit will shut down.

The Aux Start On Dly can be programmed from

0 to 120 seconds. This option is locate in the

Configuration Menu (Section 3).

2.6.10 FAULT RELAY

The fault relay is a single pole double throw

(SPDT) relay having a normally open and

normally closed set of relay contacts that are

rated for 5 amps at 120 VAC and 5 amps at 30

VDC. The relay energizes when any fault

condition occurs and remains energized until the

fault is cleared and the

CLEAR button is

depressed. The fault relay connections are

shown in Figure 2.11.

2.6.11 AUXILIARY RELAY CONTACTS

Each unit is equipped with a single pole double

throw (SPDT) relay that is energized when there

is a demand for heat and de-energized after the

demand for heat is satisfied. The relay is

provided for the control of auxiliary equipment,

such as pumps and louvers, or can be used as a

unit status indictor (firing or not firing). Its

contacts are rated for 120 VAC @ 5 amps.

Refer to Figure 2.11 to locate the AUX RELAY

terminals for wiring connections.

mA OUT

RS-485

COMM.

+

-

+

-

ANALOG IN

SENSOR COMMON

OUTDOOR SENSOR IN

REMOTE INTL'K IN

B.M.S. (PWM) IN

SHIELD

+

-

+

-

AUX SENSOR IN

NOT USED

EXHAUST SWITCH IN

DELAYED INTL'K IN

FAULT RELAY

120 VAC, 5A, RES

AUX RELAY

120 VAC, 5A, RES

G

RELAY CONTACTS:

120 VAC, 30 VDC

5 AMPS RESISTIVE

DANGER

120 VAC USED

IN THIS BOX

NOT USED

NOT USED

NC

COM

NO
NC

COM

NO

NOT USED

Figure 2.11 I/O Box Wiring

Advertising