Figure 6.1, Spark igniter and flame detector location, Maintenance – AERCO KC1000 Heater Mar 2011 User Manual

Page 46

Advertising
background image

MAINTENANCE

6-2

FLAME

DETECTOR

PROBE

LOWER

BURNER

SHELL

BURNER

HEAD

BURNER

PLATE

IGNITER

(124570)

FLAME DETECTOR

(124837)

STAGED

IGNITION

ORIFICE

Figure 6.1

Spark Igniter and Flame Detector Location

Table 6-1. Maintenance Schedule

Section

Item

6 Mos.

12 Mos.

24 Mos.

Labor Time

6.2

Spark Igniter

(124570)

Inspect

Replace

15 mins.

6.3

Flame Detector

(124837)

Inspect

Replace

15 mins.

6.4

Combustion

Adjustments.

Check

Check

1 hr.

6.5

Testing of Safety

Controls

Test

20 mins.

6.6

BTU Transmitter

Pump

Oil

15 mins.

6.7

BTU Transmitter

Inspect & clean if

necessary

50 mins.

6.8

*Manifold &

Tubes

Inspect & clean if

necessary

4 hrs.

6.9

Heat Exchanger

**

Inspect

Inspect and

Clean (as

required)

Inspect and Clean

(as required)

1.5 to 3.5 hrs.

6.10

Condensate

Drain

Inspect

Inspect &

Clean

30 mins.

6.11

Low Water Cutoff

Probe (69126)

Inspect

Inspect

Replace (Every 24

Mos.)

20 mins.

*

Recommended only when unit will be run in an extreme condensing mode for prolonged periods of time.

**

In areas where water quality is poor or not qualified, inspection and cleaning may be required to assure

trouble-free operation. Hard water deposits must be removed to prevent corrosion and leaking. Checking

at more frequent intervals may be required to prevent scale buildup. See page 6-13 for information about

removing scale deposits using AERCO HydroSkrub scale remover.