Troubleshooting – AERCO KC1000 Heater Mar 2011 User Manual

Page 72

Advertising
background image

TROUBLESHOOTING

7-8

KC1000 WATER HEATER TROUBLESHOOTING TABLE – Continued

FAULT INDICATION

PROBABLE CAUSES

CORRECTIVE ACTION

(continued)

4. Defective Power Supply

Board or fuse

5. Defective IGST Board

4. Check DS1 & DS2 LEDs on Power Supply

Board. If they are not steady ON, replace

Power Supply Board.

5. Check “Heartbeat” LED DS1 and verify it is

blinking ON & OFF every second. If not,

replace IGST Board.

PRG SWTCH OPEN

DURING PURGE

1. Defective purge switch.

2. No voltage present at

switch.

3. Switch wired incorrectly.

4. Defective Power Supply

Board or fuse

5. Defective IGST Board

1. If the air-fuel valve does rotate, check the

purge switch for continuity when closing.

Replace switch if continuity does not exist.

2. Measure for 24 VAC from each side of the

switch to ground. If 24VAC is not present, refer

fault to qualified service personnel.

3. Check to ensure that the switch is wired

correctly (correct wire numbers on the normally

open terminals).

4. Check DS1 & DS2 LEDs on Power Supply

Board. If they are not steady ON, replace

Power Supply Board.

5. Check “Heartbeat” LED DS1 and verify it is

blinking ON & OFF every second. If not,

replace IGST Board.

REMOTE SETPT

SIGNAL FAULT

1. Remote setpoint signal not

present:

Not yet installed.

Wrong polarity.

Signal defective at source.

Broken or loose wiring.

2. Signal is not isolated

(floating) if 4 to 20 mA.

3. Control Box signal type

selection switches not set

for correct signal type

(voltage or current).

1. Check I/O Box to ensure signal is hooked up.

Hook up if not installed.

If installed, check polarity.

Measure signal level.

Check continuity of wiring between source and

boiler.

2. Check signal at source to ensure it is isolated.

3. Check DIP switch on PMC board to ensure it is

set correctly for the type of signal being sent.

Check control signal type set in Configuration

Menu.

RESIDUAL

FLAME

1. SSOV not fully closed.

2. Defective Flame Detector.

1. Check open/close indicator window of Safety

Shut-Off Valve (SSOV) and ensure that the

SSOV is fully closed. If not fully closed, replace

the valve and or actuator.

Close gas shut-off valve downstream of SSOV.

Install a manometer or gauge in a gas test port

between the SSOV and the gas shut off valve.

If a gas pressure reading is observed replace

the SSOV valve and or actuator.

2. Replace Flame Detector.

SSOV FAULT

DURING PURGE

1. See SSOV SWITCH OPEN

Advertising