Tuning menu, Control panel operating procedures – AERCO KC1000 Low NOx Water Heater July 2011 User Manual

Page 25

Advertising
background image

CONTROL PANEL OPERATING PROCEDURES

3-7

Table 3-4. Configuration Menu - Continued

Available Choices or Limits

Menu Item Display

Minimum

Maximum

Default

Low Fire Timer

2 sec.

600 sec.

2 sec.

Setpt Limiting

Enabled or Disabled

Disabled

Setpt Limit Band

0°F

10°F

5°F

Network Timeout

5 Sec

999 Sec

30 Sec

HI DB Setpt EN

0%

100%

30%

Demand Offsert

0

25

10

Deadband High

0

25

2

Deadband Low

0

25

2

*CAUTION:

DO NOT CHANGE the Analog Output Menu Item from its Default setting

(Valve Position 0-10V).

3.7. TUNING MENU

The Tuning Menu items in Table 3-5 are Factory

set for each individual unit.


Do not change these menu entries unless

specifically requested to do so by factory trained

personnel.

Table 3-5. Tuning Menu

Available Choices or Limits

Menu Item Display

Minimum

Maximum

Default

Min Load Adj

-50°F

50°F

0°F

Max Load Adj

-50°F

50°F

0°F

FFWD Temp

30°F

245°F

Outlet Feedback

On

Off

On

Reset Defaults?

Yes

No

Are You Sure?

No