Troubleshooting – AERCO KC1000 Low NOx Water Heater July 2011 User Manual

Page 73

Advertising
background image

TROUBLESHOOTING

7-9

KC1000 WATER HEATER TROUBLESHOOTING TABLE – Continued

FAULT INDICATION

PROBABLE CAUSES

CORRECTIVE ACTION

SSOV FAULT

DURING RUN

1. SSOV switch closed for 15

seconds during run.

1. Replace SSOV actuator.

SSOV RELAY

FAILURE

1. SSOV relay failed on

board.

2. Floating Neutral.

3. Hot and Neutral reversed

at SSOV

1. Ensure that Neutral and Earth Ground are

connected at the source and there is no voltage

measured between them. Measurement should

indicate near zero or no more than a few

millivolts.

2. Check the SSOV power wiring.
3. Press CLEAR button and restart unit. If fault

persists, replace Ignition/Stepper (IGST) Board.

SSOV

SWITCH OPEN

1. Actuator not allowing for

full closure of gas valve

2. SSOV powered when it

should not be

3. Defective Switch or

Actuator

4. Incorrectly wired switch.

1. Observe operation of the Safety Shut-Off Valve

(SSOV) through indicator on the Valve actuator

and ensure that the valve is fully and not partially

closing.

2. If the SSOV never closes, it may be powered

continuously. Close the gas supply and remove

power from the unit. Refer fault to qualified

service personnel.

3. Remove the electrical cover from the SSOV and

check switch continuity. If the switch does not

show continuity with the gas valve closed, either

adjust or replace the switch or actuator.

4. Ensure that the SSOV Proof of Closure switch is

correctly wired.

STEPPER MOTOR

FAILURE

1. Air/Fuel Valve out of

calibration.

2. Air/Fuel Valve unplugged.

3. Loose wiring connection to

the stepper motor.

4. Defective Air/Fuel Valve

stepper motor.

5. Defective Power Supply

Board or fuse.

6. Defective IGST Board

1. Refer to GF-112 and perform Stepper Test (para.

6.3.5) to ensure stepper motor rotates properly

between the 0% (fully closed) and 100% (fully

open) positions. Verify that the VALVE POSITION

bargraph and the dial on the Air/Fuel Valve track

each other to indicate proper operation. If

operation is not correct, perform the Stepper

Feedback Calibration (GF-112, para. 6.2.1).

2. Check to ensure that the Air/Fuel Valve is

connected to the Control Box.

3. .Inspect for loose connections between the

Air/Fuel Valve motor and the wiring harness.

4. Replace stepper motor.

5. Check DS1 & DS2 LEDs on Power Supply Board.

If they are not steady ON, replace Power Supply

Board.

6. Check “Heartbeat” LED DS1 and verify it is

blinking ON & OFF every second. If not, replace

IGST Board.