INITIAL START-UP

4-9

5. Make small adjustments and allow time

between adjustments for the outlet water

temperature to stabilize.

6. Maintain water flow as constant as possible

during these adjustments.

7. Ensure that recirculation loops are

operational while the calibration is being

performed.

4.6.1 SETTING THE OUTLET WATER

TEMPERATURE SETPOINT

The setpoint temperature of the unit may be

changed by following the procedure below.

However, once a setpoint has been changed,

recalibration may be necessary. The

temperature calibration procedures are provided

in paragraphs 4.6.2 and 4.6.3

To adjust the unit’s setpoint, proceed as follows:
1. Press the

MENU key until Configuration

Menu is displayed.

2. Press the ▲ or ▼ arrow key until Internal

Setpt is displayed along with the present

setpoint temperature.

3. To change the setpoint, press the

CHANGE

key. The display will begin to flash.

4. Press the ▲ or ▼ arrow key until the

desired setpoint is displayed.

5. Press the ENTER key to save the change.

4.6.2 MINIMUM LOAD ADJUSTMENT

With the unit in operation, check the temperature

control at minimum load as follows:

1. While monitoring the

VALVE POSITION

display, create a minimum load on the

system that will yield a steady valve position

between 25% and 35%.

NOTE:

It may be desirable to shut off the outlet valve

and use the hose bib to simulate a minimum flow

load condition.

2. Wait several minutes to allow the outlet

temperature to stabilize under load

conditions.

3.

Once stabilized, the

OUTLET TEMPER-

ATURE display should read no more than 2

to 3 degrees above the unit’s setpoint.

4.

If the outlet temperature is stabilized,

proceed to the Maximum Load Adjustment

procedure in paragraph 4.6.3. If the unit is

not stabilized, proceed to step 5.

5.

Press the

MENU key and select the Tuning

Menu.

6.

Press the ▲ or ▼ arrow key until Min Load

Adj is displayed.

7.

Press the

CHANGE key. The display will

begin to flash.

8.

Raise or lower the minimum load adjustment

in increments of one or two using the ▲ or

▼ arrow key. Increasing this value will

increase outlet water temperature, while

decreasing it will decrease outlet water

temperature.

9.

Press

ENTER to save the change. Allow

time for the system to stabilize between

adjustments

10. Repeat steps 5 through 9 as needed until

the temperature is stabilized at no more than

2 to 3 degrees above the setpoint.

4.6.3 MAXIMUM LOAD ADJUSTMENT

Check the temperature control at maximum load

as follows:

1. While monitoring the

VALVE POSITION

display, create a maximum load on the

system that will yield a steady valve position

between 80% and 90%.

NOTE:

It may be necessary to open the outlet valve if it

was closed during minimum load adjustment to

obtain a sufficient flow rate for maximum

adjustment.

2. Wait several minutes to allow the outlet

water temperature to stabilize under load

conditions.

3. Once stabilized, the

OUTLET TEMPER-

ATURE display should read no more than 2

to 3 degrees below the unit’s setpoint.

4. If the outlet temperature is stabilized, no

adjustment is necessary. If the unit is not

stabilized, proceed to step 5.

5. Press the

MENU key and select the Tuning

Menu.

6. Press the ▲ or ▼ arrow key until Max

Load Adj is displayed.