Appendix b – AERCO KC1000 Low NOx Water Heater July 2011 User Manual

Page 85

Advertising
background image

APPENDIX B

B-3

TABLE B-2. FAULT MESSAGES - Continued

FAULT MESSAGE

FAULT DESCRIPTION

OUTDOOR TEMP

SENSOR FAULT

The temperature measured by the Outdoor Air Sensor is out

of range.

OUTLET TEMP

SENSOR FAULT

The temperature measured by the Outlet Sensor is out of

range:

OUTLET TEMPERATURE display = SHt Indicates sensor

is shorted

OUTLET TEMPERATURE display = OPn indicates sensor

is open-circuited

PRG SWTCH CLOSED

DURING IGNITION

The Purge Position Limit Switch on the Air/Fuel Valve closed

during ignition.

PRG SWTCH OPEN

DURING PURGE

The Purge Position Limit Switch on the Air/Fuel Valve

opened during purge.

REMOTE SETPT

SIGNAL FAULT

The Remote Setpoint signal is not present or is out of range.

RESIDUAL

FLAME

The Flame signal was seen for more than 60 seconds during

standby.

SSOV

SWITCH OPEN

The SSOV switch opened during standby.

SSOV FAULT

DURING PURGE

The SSOV switch opened during purge.

SSOV FAULT

DURING IGN

The SSOV switch closed or failed to open during ignition.

SSOV FAULT

DURING RUN

The SSOV switch closed for more than 15 seconds during

run.

SSOV RELAY

FAILURE

A failure has been detected in one of the relays that control

the SSOV.

STEPPER MOTOR

FAILURE

The Stepper Motor failed to move the Air/Fuel Valve to the

desired position.

Advertising