Removing the heater shell, Removing coils and risers, 1b+ ii water wizard water heaters he-110 – AERCO Packaged WaterWizard Steam-to-Water Heater User Manual

Page 33

Advertising
background image

1B+ II Water Wizard Water Heaters

HE-110

Installation, Operation & Maintenance Manual

OMM-0063_0C

MC2: 07/26/13 Page 33 of 50

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, New York 10913 • Phone: 800-526-0288

10.6. REMOVING THE HEATER SHELL

Remove the Heater Shell as follows:




















10.7. REMOVING COILS AND RISERS

The Coil Assemblies, Riser and Condensate Return are removed as follows:
























Heater Shell Removal Instructions

1) Using a black marker, mark the edge of the Heater Bottom Head flange and Shell flange in order to

indicate their correct relative positions upon reassemble. The Top Head can remain attached to the
Shell.

2) Using the 1-1/16” combination wrench, unbolt the sixteen studs and nuts around the bottom ring of the

Shell. The two nuts located in-line with the mounting skid legs are to be removed with the stud left in
place.

3) Attach a chain hoist to the two lifting lugs on the Top Head. Lift the Shell up to clear the internal coil

bundle.

4) Using a light source, visually inspect the inside of the Heater Shell for evidence of damage to the

Copper Shell Liner. If any area of the Copper Liner is damaged, replace the Shell down on the Bottom
Head and contact your local AERCO Representative to process return of the Heater to AERCO for
repair.

5) Move the heat exchanger bundle a few feet to the side so that the Shell can be lowered to the floor.

Set the Shell on clean surface. Use care to avoid damaging the bottom edge of the Copper Shell Liner.

Removal of Coils and Risers Instructions

1) Using the proper size open-end wrench, loosen the two Union Nuts securing the Coils to the

Steam Riser and Condensate Return.

2) Using a pipe wrench, remove the Steam Riser and Condensate Return from the Bottom Head.

Advertising