Sk-acp installation & operating manual – American Access Systems ProAccess 200sa User Manual

Page 29

Advertising
background image

SK-ACP

Installation & Operating Manual

b) Pin 3 (Clear to Send, CTS). The voltage should read between +5 VDC to +12 VDC. This voltage

comes from the PC. If the voltage is wrong or missing, disconnect the reader from the PC, and
measure the voltages at the reader (should be 0.0 VDC) and at the PC (should be between +5
VDC to +12 VDC).

c) Pin 4 (Request to Send, RTS). The voltage should read between -5 VDC to -12 VDC. This

voltage comes from the Card Reader. If the voltage is wrong or missing, disconnect the reader
from the PC, and measure the voltages at the reader (should be -9.5 VDC) and at the PC
(should be 0.0 VDC).

d) Pin 5 (Transmit Data, TXD). The voltage should read between -5 VDC to -12 VDC. This voltage

comes from the Card Reader. If the voltage is wrong or missing, disconnect the reader from the PC,
and measure the voltages at the reader (should be -9.5 VDC) and at the PC (should be 0.0 VDC).

After testing voltages, return to the Location/Properties/Connection box and re-check the box next to “Gateway (RS-232)”.

3.4

Power Reset (for initial setup only!)

1. Power Reset: This will change the node address, set password to 12345 (default), and set the

baud rate to 38,400 (default).
a) Turn off the power to the reader, push the reset button, turn on the power with reset button pushed

for approximately 3 seconds after turning on power. Do not have any cards near the reader while
this process is being done. Repeat for all readers.

3.5

Steps to find new readers

1. Right click on location name.

2. Select Connect. Message on Screen: “Connecting to location (Name), continue.” Click OK.

3. Message on Screen: “There are no readers in Location (Name). To be logged in, scan for new readers now?”

Click YES. Message on screen: “Are there more than 20 readers in this location? Select “YES” or “NO”.

4. Message on Screen: “New Readers Found!”, select OK. Now the software will make backup files for

all the settings in all of the readers except for the card status.

Recommended Tools & Supplies

1)

Laptop PC

2)

CBLSA Cable Kit

3)

Multimeter to measure DC volts and resistance

4)

Hand tools required for the reader installation, and connection.

Tech Support Options

Web Page: www.securakey.com • E-Mail: [email protected]
Fax: 818-882-7052 • Toll-Free Telephone: 800-891-0020
Tech Support Hours: 7:30 am to 5:00 pm P.S.T. • Best Time to call: Afternoons P.S.T.