Figure 4: troubleshooting flow chart (1 of 2) – BASO BG1100M User Manual

Page 8

Advertising
background image

8 BG1100M Direct Spark Ignition Control Installation Instructions

Yes

No

No

Yes

Turn on power

and gas.

Close thermostat

contacts.

Module red LED

did not light and

no spark?

Module red LED

blinks slowly?

Diagnostic error

see next page.

Replace module.

24V between
TH and GND

terminals?

Yes

No

Yes

Module red LED

blinks rapidly but

no spark?

Check transformer,

thermostat and wiring.

Repair or replace as needed.

Replace

module.

No

Spark wire

and electrode

OK?

Replace

module.

Replace spark wire

or electrode.

Yes

Yes

No

Flame

does not

light?

24V between

valve and GND

terminals?

Replace

module.

Gas at

burner?

Yes

Yes

No

Check shutoff valves are on.

Check wiring to valve.

Check orifice and tubing are clear.

If all OK replace pilot valve.

Adjust or replace spark

electrode and/or pilot

burner.

No

Burner lights

but keeps
sparking?

Burner flame in contact

with spark or sense

electrode?

No

Yes

Yes

Replace

module.

No

Check burner orifice.

Adjust pilot flame size or

electrode position.

Two rod

flame sense?

Yes

Check wiring electrode

to SENSE terminal.

If OK replace module.

Burner is lit

continued

on next page

No

No

Figure 4: Troubleshooting Flow Chart (1 of 2)