When the voltages of individual cells are lower than normal, it is
possible to conclude that insufficient charging has occurred.

The following are possible causes of cell voltage variations:

• Panel voltmeter reading high - This results in a low float voltage.

Re-calibrate the panel voltmeter.

• Poor intercell/inter-unit or terminal connections - If any

connection is found to be higher than 20% of the initial installation
values, disassemble and clean contact surfaces and reassemble.

• A temperature variation of more than 5°F (2.8°C) between cells -

Warmer cells drop to a lower voltage, because they require more
float current to keep them fully charged. Avoid exposing batteries to
external heat sources, which can cause temperature imbalance.

3.4 Effects of temperature

A lead-acid battery is an electro chemical device. Heat accelerates
chemical activity; cold slows it down. Normal battery operating
temperature is 77°F (25°C). Higher than normal temperatures have
the following effects on a lead-acid battery:
• Increases capacity
• Shortens life
• Increases internal discharge or local action losses
• Lowers cell voltage for a given charge current
• Raises charging current for a given charge voltage
• Increases the rate of dry-out of electrolyte

Lower than normal temperatures have the opposite effect and reduce
capacity. In general, at proper float voltage, a battery in a cool
location will last longer than one in a warm location.

Note: No temperature correction is required when operating at 77°F

+/- 10°F, (25°C +/- 5.5°C). The following correction factors
apply for a range not exceeding +/- 30°F from nominal. For
further
assistance with temperature correction factors, contact C&D
Technologies.

If the operating temperature is other than 77°F (25°C), it is recommend-
ed that the float voltage be changed as follows:

For temperatures other than 77°F (25°C), correct float voltage by 2
mV per degree F (3.6 mV per degree C):

• Add 2 mV (0.002 Volts) per degree F (3.6 mV per degree C) below

77°F (25°C)

• Subtract 2 mV (0.002 Volts) per degree F (3.6 mV per degree C)

above 77°F (25°C)

Note: Temperature compensation will materially improve battery

service life when provided.