25

completely recharge the battery and take a set of voltage readings,
recording them for future reference if the readings are satisfactory.
Provide remedial action or an equalize charge if necessary.

Do not

discharge a battery below the design final voltage. Remedial
action may be required if the battery was discharged below its final
design voltage. Very deep discharges can, without an immediate
recharge, completely deplete the electrolyte and cause hydration.

Note: Refer to sample form RS-1511 found in the Appendix to record

readings.

1. BATTERY IDENTIFICATION
2. DATE OF REPORT
3. BATTERY FLOAT VOLTAGE
4. AMBIENT OPERATING AND STORAGE TEMPERATURES
5. DATE AND DESCRIPTION OF LAST EQUALIZING CHARGE (IF

APPLICABLE)

6. GENERAL OBSERVATIONS FROM VISUAL INSPECTION AND

INDIVIDUAL CELL VOLTAGES

7. NAME OF INSPECTING TECHNICIAN

If any unusual readings or visual indications are observed, consult
your C&D Technologies representative and send a copy of your latest
maintenance report to the Technical Services Department, C&D
Technologies, Inc., 1400 Union Meeting Road, Blue Bell,
PA 19422. Indicate to whom you have spoken in C&D
Technologies sales and service and when your battery was
last inspected.