Appendix B - WARRANTY PROVISIONS FOR LIBERTY SERIES

1000 BATTERIES

C&D Technologies valve regulated lead-acid batteries are warranted
against defects in materials or manufacturing or both from C&D factory
when operated in full float and when stored at 77°F (25°C). Refer to
specific warranty certificates for your Liberty 1000 model for float or
UPS operation and for storage at other temperatures.

IMPORTANT: Full and pro-rata warranty is reduced for operation
exceeding 77°F (25°C) and is adjusted for cycle service (such as UPS
service and similar applications). Refer to the specific warranty
RS-924 for full float service and RS-1224 for cycle service (such as
UPS) provided in the time period when the battery was purchased.

Always complete the record of initial charge, float charge and ambient
temperature as described in the initial charge section of this manual
and retain them in your files for future reference. Clearly identify your
location, application, C&D Technologies model number, the date, and
name of the person who took the readings.

The service life of your battery will depend on ambient temperature,
frequency and depth of discharge, discharge rate, charge voltage, and
regulation of the battery charger. A product warranty is available by
writing C&D Technologies, Inc., 1400 Union Meeting Road, PO Box
3053, Blue Bell, PA 19422-0858.

CAUTION

Due to the operating requirements of valve-regulated batteries,
Liberty Series 1000 batteries are sealed and hydrometer
readings cannot be taken. Removal of vents voids warranty.