Campbell Scientific SDM-SW8A 8-Channel Switch Closure Input Module User Manual

Page 12

Advertising
background image

SDM-SW8A Switch Closure Input Module

The syntax of this instruction is as follows:

SDMSpeed (

BitPeriod

)

The BitPeriod argument can be an integer or a variable. If the SDMSpeed
instruction is not in the program, a default bit period is used. If 0 is used for
the argument, the minimum allowable bit period is used. Table 5 shows the
default, minimum allowable, and maximum bit period for each of our CRBasic
dataloggers.

TABLE 5. Bit Period Values


Datalogger

Default
Bit Period

Minimum Allowable
Bit Period

Maximum
Bit Period

CR800, CR850 26.04

μsec 8.68

μsec

2.2 msec

CR1000

26.04

μsec 8.68

μsec

2.2 msec

CR3000

26.04

μsec 8.68

μsec

2.2 msec

CR5000

30

μsec 8

μsec

3 msec

The equation used to calculate the bit rate depends on the datalogger used.
The datalogger will round down to the next faster bit rate.

Equation for CR800, CR850, and CR1000:

bit_rate=INT((k*72)/625)*Resolution

Where:
k= the value entered in BitPeriod

Resolution=8.68 microseconds

Equation for CR3000:

bit_rate=INT((k*144)/625)*Resolution

Where:
k= the value entered in BitPeriod
Resolution= 4.34

μsec.

Equation for CR5000:

bit_rate=INT(k*20)*Resolution

Where:
k= the value entered in BitPeriod
Resolution=50 nsec.

8