SDM-SW8A Switch Closure Input Module

4. Connections

All connections to the datalogger, power supply, and other SW8As are made
from terminals located under "TO DATALOGGER" on the SW8A (refer to
Figure 1). Sensor connections are made at the remaining terminals.

4.1 Connections to Dataloggers and Other SW8As

The CABLE5CBL or a similar cable is used to connect the SDM-SW8A to a
datalogger.

Connections between an SW8A and a datalogger are shown in Table 1.
Connections to multiple SW8As are shown in Table 2.

1. The order in which connections are made is critical.
ALWAYS CONNECT GROUND FIRST, followed by 12 V
and then the Control Ports.

CAUTION

2. The sum of all the cable lengths connecting SW8As or
other SDM devices and a datalogger should be as short as
possible and preferably does not exceed 20 ft. Longer
lead lengths may be possible for CRBasic dataloggers if
the SDMSpeed instruction is used (see Section 6.1.2).
Long lead lengths may prevent communication.

4.2 Sensor Connections

Figure 2 shows the connections between the SW8A and compatible sensor
types.

5. Internal Jumpers

Inside the SW8A, jumpers must be set to configure the Module address and the
channel measurement type for each channel. Remove the two panel screws
and lift the cover to access the jumpers. Figure 2 shows jumper location.

5.1 Address Jumpers

Each module can have 1 of 16 addresses (00 to 33, Base 4). The address is
factory set to 00. Figure 2 shows the location of the address jumper block.
Table 3 lists the jumper settings for each address.