12 CHECK OUT THERMOSTAT OPERATION'

CAUTIONS

Do NOT check operation by shorting across ter­
minais of relay or valve coil; this will burn out the
thermostat heat anticipator.

HEATING-ONLY SYSTEM

HU

Turn on power to the furnace.

[Z] Push both temperature setting levers together at

least 5 F [3 C] above room temperature. The main

burner should come on. The fan will start when the fur­

nace heats up.

Move both levers 5 F [3 C] below room tempera­

ture. The burner should shut off.

Q Operate the entire heating system at least one
oompíete cycle.

D

IF THERMOSTAT FAILS ANY TEST, REFER TO

TROUBLESHOOTING

GUIDE

IN

THE

OWNER'S

MANUAL.

Reset both temperature setting levers to desired

temperatures.

HEATING/COOLING SYSTEM

n Turn on power to the furnace and cooling system.

n Place the system switch lever at HEAT and fan

switch lever at AUTO.

[m Push both temperature setting levers together at

least 5 F [3 C] above room temperature. The main

burner should come on. The fan will start when the fur­

nace heats up. (If central electric heat system, fan starts
immediately.)

Move both levers 5 F [3 C] below room tempera­

ture. The burner should shut off.

Place the system switch lever at COOL and the

fan switch lever at AUTO. The cooling equipment should
operate, and the fan will start. Allow for any time delay
that may be built into the compressor control circuit.

NOTE: To avoid compressor damage, do not operate

the system if outdoor temperature is below 50 F

[10 0]. Refer to manufacturer’s recommendations.

□ Move both temperature setting levers together at

least 5 F [3 C] above room temperature. The cooling
equipment should shut off.

Place the fan switch at ON. The fan should run

continuously with the system switch in any position.

HH Place the system switch at OFF. Move both

temperature setting levers to various positions. The

heating and cooling systems should not operate.

Operate the entire system for at least one com­

plete cycle with the system switch at COOL and one
complete cycle with the switch at HEAT.

D IF THERMOSTAT FAILS ANY TEST, REFER TO

TROUBLESHOOTING

GUIDE

IN

THE

OWNER'S

MANUAL

Reset both temperature setting levers to desired

temperatures.

LEAVE OWNER’S MANUAL, ASSISTANCE INFORMA­

TION, AND REPLY CARD IN A CONVENIENT PLACE

FOR THE BUILDING OCCUPANT OR PROVIDE WITH

OTHER APPLIANCE MANUALS.

TYPICAL WIRING DIAGRAMS------------------

Follow the hookup diagram supplied with your heat­

ing or heating/cooling equipment. If not available, use

the following diagrams as a guide.

REMEMBER: Your wiring must follow local electrical

codes and ordinances.

THERMOSTAT

Ai

Fig. 11 —Hookup showing a typical 24 V, gas heating

control system.